Configuration menu (ConF)<br />
*: Write only when the soft starter is stopped<br />
50<br />
Code Name/Description R/W Adjustment range Factory setting<br />
conF Configuration menu<br />
IcL • Soft starter rated current R According to the soft<br />
starter rating<br />
Maximum rated continuous current of the soft starter (see pages 11 to 84).<br />
IcL value is on the soft starter nameplate (Soft starter FLA). Read only parameter between 17 A and 590 A.<br />
dLtA • Connection type<br />
LInE<br />
dLt<br />
CAUTION<br />
RISK OF DAMAGE TO THE SOFT STARTER<br />
• This parameter must be set in accordance with the wiring type, see page 30.<br />
• When dLtA is set to dLt:<br />
- Only the SH31-.../4 range can be installed inside delta connection.<br />
- Ensure connection exactly as shown page 30.<br />
- Line voltage should not exceed 440 V.<br />
Failure to follow these instructions can result in equipment damage.<br />
Uln • Line voltage<br />
- Line: in line connection<br />
- Inside delta connection of the motor.<br />
Parameters automatically set when dLtA = dLt<br />
Parameter Set Description<br />
code value<br />
bSt 0 Boost time, see page 53<br />
SSC oFF Start-stop control, see page 54<br />
SPCU 0 Start-stop profile control voltage, see page 54<br />
PHr 123 Phase sequence, see page 57<br />
EdC inactive End of deceleration, see page 52<br />
R/W* LInE<br />
R/W /4 range:<br />
200 to 440 V<br />
/6 range:<br />
200 to 600 V<br />
/4 range:<br />
400 V<br />
/6 range:<br />
480 V<br />
Set to the nominal voltage of the mains.<br />
Note: Improper setting may cause unnecessary tripping, because Uln is the reference for over voltage and under<br />
voltage protections.<br />
In • Motor rated current<br />
Cod • Setting lock<br />
nLOC<br />
LOC<br />
R/W* 0.4 IcL<br />
up to IcL<br />
• Soft starter in line connection:In = rated current of the motor.<br />
• Soft starter inside delta connection:In = rated current of the motor / √3.<br />
R/W nLOC<br />
According to the<br />
soft starter rating<br />
(pages 11 to 22)<br />
Used to enable or disable parameters modification on the displays.<br />
- not locked: all R/W parameters can be modified. Also accessible with key combination<br />
- locked: all parameters are read only on local display or remote keypad display (the parameters can be<br />
still modified by serial link and BLEMOsoft software).<br />
LAC • Advanced mode<br />
oFF<br />
On<br />
R/W oFF<br />
Allows you to access to the Advanced level, see page 46 for detailed description.<br />
- off: Easy start up level<br />
- on: Advanced level<br />
Note: It also allows to display a longer trip history list:<br />
LAC set to oFF: Total number of trips dEFtand Trip history 1 dEF1, page 63.<br />
LAC set to On: Total number of trips dEFt and Trip history 1 dEF1 to Trip history 9 dEF9, page 63.