Configuration menu (ConF)<br />

*: Write only when the soft starter is stopped<br />

50<br />

Code Name/Description R/W Adjustment range Factory setting<br />

conF Configuration menu<br />

IcL • Soft starter rated current R According to the soft<br />

starter rating<br />

Maximum rated continuous current of the soft starter (see pages 11 to 84).<br />

IcL value is on the soft starter nameplate (Soft starter FLA). Read only parameter between 17 A and 590 A.<br />

dLtA • Connection type<br />

LInE<br />

dLt<br />

CAUTION<br />

RISK OF DAMAGE TO THE SOFT STARTER<br />

• This parameter must be set in accordance with the wiring type, see page 30.<br />

• When dLtA is set to dLt:<br />

- Only the SH31-.../4 range can be installed inside delta connection.<br />

- Ensure connection exactly as shown page 30.<br />

- Line voltage should not exceed 440 V.<br />

Failure to follow these instructions can result in equipment damage.<br />

Uln • Line voltage<br />

- Line: in line connection<br />

- Inside delta connection of the motor.<br />

Parameters automatically set when dLtA = dLt<br />

Parameter Set Description<br />

code value<br />

bSt 0 Boost time, see page 53<br />

SSC oFF Start-stop control, see page 54<br />

SPCU 0 Start-stop profile control voltage, see page 54<br />

PHr 123 Phase sequence, see page 57<br />

EdC inactive End of deceleration, see page 52<br />

R/W* LInE<br />

R/W /4 range:<br />

200 to 440 V<br />

/6 range:<br />

200 to 600 V<br />

/4 range:<br />

400 V<br />

/6 range:<br />

480 V<br />

Set to the nominal voltage of the mains.<br />

Note: Improper setting may cause unnecessary tripping, because Uln is the reference for over voltage and under<br />

voltage protections.<br />

In • Motor rated current<br />

Cod • Setting lock<br />

nLOC<br />

LOC<br />

R/W* 0.4 IcL<br />

up to IcL<br />

• Soft starter in line connection:In = rated current of the motor.<br />

• Soft starter inside delta connection:In = rated current of the motor / √3.<br />

R/W nLOC<br />

According to the<br />

soft starter rating<br />

(pages 11 to 22)<br />

Used to enable or disable parameters modification on the displays.<br />

- not locked: all R/W parameters can be modified. Also accessible with key combination<br />

- locked: all parameters are read only on local display or remote keypad display (the parameters can be<br />

still modified by serial link and BLEMOsoft software).<br />

LAC • Advanced mode<br />

oFF<br />

On<br />

R/W oFF<br />

Allows you to access to the Advanced level, see page 46 for detailed description.<br />

- off: Easy start up level<br />

- on: Advanced level<br />

Note: It also allows to display a longer trip history list:<br />

LAC set to oFF: Total number of trips dEFtand Trip history 1 dEF1, page 63.<br />

LAC set to On: Total number of trips dEFt and Trip history 1 dEF1 to Trip history 9 dEF9, page 63.