GETCO/E/TS – XMER01power/R4 Sept <strong>08</strong><br />

b) Passage of air is possible through silica gel <strong>on</strong>ly<br />

c) Height of breather mounting shall not be less than 1200 mm from rail top<br />

level<br />

d) Size of breather shall be such that it c<strong>on</strong>tent 5 kG of silica gel in it<br />

e) The nos. of breathers shall be Three or more as required for main<br />

c<strong>on</strong>servator and shall be Two for OLTC c<strong>on</strong>servator<br />

f) Silica gel is isolated from atmosphere by an oil seal.<br />

(xix)<br />

C<strong>on</strong>servator and Buchholz (Surge) relay for <strong>on</strong> load tap changer.<br />

(xx) Suitable terminal c<strong>on</strong>nectors for HV, LV & Neutral bushings<br />

(xxi) Suitable ladder or climbing devices.<br />

(xxii) Tap changer remote c<strong>on</strong>trol panel complete with all accessories to be installed<br />

in the purchaser’s c<strong>on</strong>trol room.<br />

(xxiii) A twin tinned copper strip grounding c<strong>on</strong>ductor of 50 x6 mm size shall be<br />

provided from the neutral terminal to transformer base for c<strong>on</strong>necti<strong>on</strong> to the<br />

sub-stati<strong>on</strong> grounding grid. Necessary pin insulator clamps, bolts etc. shall be<br />

supplied for this grounding purpose. Neutral bushing to grounding<br />

c<strong>on</strong>ductor shall be made through twin copper flexible strip of size 50 x<br />

10 mm.<br />

xxiv) Inspecti<strong>on</strong> opening and covers<br />

xxv) Protected type mercury or alcohol in glass thermometer<br />

xxvi) Bottom and top filter valves with threaded male adaptors, bottom<br />

xxvii) Rating and diagram plates <strong>on</strong> transformer and auxiliary apparatus<br />

xxviii) Flanged bi-directi<strong>on</strong>al wheel with anti earth quake clamps<br />

xxix) Cooler c<strong>on</strong>trol cabinet<br />

xxx) Bushing CTs<br />

xxxi) Oil flow Indicator<br />

xxxii) On Load Tap Changing Gear<br />

xxxiii) Drain valves/plugs shall be provided in order that each secti<strong>on</strong> pipe work can<br />

be drained independently<br />

xxxiv) Terminal Marking plates of Stainless Steel sheet having minimum thickness<br />

of 2 MM<br />

xxxv) Valves Schedule plates of Stainless Steel sheet having minimum thickness<br />

of 2 MM<br />

Any other fitting / accessories other than listed above, required for satisfactory<br />

operati<strong>on</strong> of the transformer are deemed to be included<br />

1.22.2 The equipment and accessories furnished with the transformer shall be suitably<br />

mounted <strong>on</strong> the transformer, for satisfactory operati<strong>on</strong>, inspecti<strong>on</strong> and maintenance<br />

and the mounting details shall be subject to the approval of the purchaser. All valves<br />

shall be provided either with blind compani<strong>on</strong> flanges or with pipe plugs for<br />

protecti<strong>on</strong>.<br />

1.22.3 Indicati<strong>on</strong>, alarm and relay equipment shall have c<strong>on</strong>tacts suitable for operati<strong>on</strong> with<br />

110 V/<str<strong>on</strong>g>220</str<strong>on</strong>g> V D.C. Supply.<br />

1.22.4 All cables from all equipment/device shall be arranged by manufacturer with proper<br />

clamping arrangement<br />

Any other accessories or appliances recommended by the manufacturer for the satisfactory<br />

operati<strong>on</strong> of the transformer, shall be given and indicated in the bid.<br />

Sign and Seal of Bidder Page 25 of 87