GETCO/E/TS – XMER01power/R4 Sept <strong>08</strong><br />

SECTION – II<br />

TECHNICAL SPECIFICATION<br />

FOR <str<strong>on</strong>g>220</str<strong>on</strong>g> kV CLASS POWER TRANSFORMERS<br />

SPECIFIC REQUIREMENTS<br />

2.1 SCOPE:<br />

2.1.1 This secti<strong>on</strong> covers the specific technical requirements, climatic and isoceranic<br />

c<strong>on</strong>diti<strong>on</strong>s and system particulars for which the power transformer shall be offered<br />

as per the general technical requirements given in Secti<strong>on</strong> – I of this specificati<strong>on</strong><br />

and the Schedule of requirements specified herein for the various sub-stati<strong>on</strong>s.<br />

2.2 CLIMATIC AND ISOCERANIC CONDITIONS:<br />

2.2.1 The climatic c<strong>on</strong>diti<strong>on</strong>s under which the equipments shall operate satisfactorily.<br />

(a) Maximum ambient temperature of air in Shade ( O C) 50<br />

(b) Minimum ambient temperature of air in shade. ( O C) 50<br />

(c) Maximum daily average ambient temperature ( O C) 40<br />

(d) Maximum yearly average ambient temperature ( O C) 30<br />

(e) Maximum relative humidity (%) 95<br />

(f) Average number of thunder storm (days/annum). 15<br />

(g) Average number rain fail (cm) 150<br />

(h) Maximum wind pressure (kg / m 2 ) 150<br />

(i) Height above m<strong>on</strong>so<strong>on</strong> level (mtr) Not exceeding<br />

1000<br />

2.2.2 All equipments offered shall be suitable for c<strong>on</strong>tinuous satisfactory operati<strong>on</strong> at the<br />

full rated capacity under the climatic c<strong>on</strong>diti<strong>on</strong>s.<br />

2.2.3 Since the sub-stati<strong>on</strong> may be near seashore or industrial area, the equipment offered<br />

shall be suitable for heavily polluted atmosphere.<br />

2.3 TYPE AND RATING:<br />

2.3.1 The transformers shall be either core or shell type c<strong>on</strong>structi<strong>on</strong>, 3 phase, oil<br />

immersed, ONAN/ONAF/OFAF with external heat exchanger and shall be suitable<br />

for outdoor services. The rating and the electrical characteristics of the transformers<br />

shall be as under:<br />

Sign and Seal of Bidder Page 40 of 87