GETCO/E/TS – XMER01power/R4 Sept <strong>08</strong><br />

Annexure - II<br />

Technical Specificati<strong>on</strong> For On Line Moisture and Gas In Oil Analyser For New<br />

Transformer With Model Analysis Software And Remote Data<br />

Transfer/Communicati<strong>on</strong>s through internet:<br />

1.0 GENERAL:<br />

The transformer shall be equipped with <strong>on</strong> <strong>line</strong> moisture and gas in oil analyzer system,<br />

‘HYDRAN – M2’ or equivalent with model analysis software and remote data transfer /<br />

communicati<strong>on</strong>s. It is intended to c<strong>on</strong>tinuously m<strong>on</strong>itor the evoluti<strong>on</strong> of dissolved gases<br />

from the oil of transformer with the help of a gas in oil sensor with no moving<br />

parts or pump to detect and c<strong>on</strong>tinuously m<strong>on</strong>itor a composite value of gases<br />

like H2 (Hydrogen), CO (Carb<strong>on</strong> m<strong>on</strong>oxide), C2H2 (Acetylene), C2H4 (Ethylene), etc.<br />

The system shall be installed <strong>on</strong> a single, open bore ball or gate valve. The<br />

system shall also c<strong>on</strong>tinuously m<strong>on</strong>itor the moisture c<strong>on</strong>tent in the transformer oil to<br />

result a comprehensive incipient fault m<strong>on</strong>itoring system.<br />

Based <strong>on</strong> the type and c<strong>on</strong>figurati<strong>on</strong> of the transformer and with 4, 4-20mA<br />

input channels and appropriate n<strong>on</strong> intrusive sensors, the system shall be<br />

capable of utilizing the measured parameters of temperature, cooling bank<br />

status and load currents to derive the following model calculati<strong>on</strong>s (based <strong>on</strong><br />

IEEE and/or IEC Standards). The original factory test report for the<br />

transformer will be made available to properly c<strong>on</strong>figure these model<br />

calculati<strong>on</strong>s.<br />

• Apparent Power<br />

• Load Current<br />

• PPM value of composite combustible gas measurement<br />

• Short term and l<strong>on</strong>g term rate of change of PPM value of composite<br />

combustible gas measurement<br />

• PPM water c<strong>on</strong>tent in oil<br />

• Water in oil c<strong>on</strong>densati<strong>on</strong> temperature<br />

• Winding hotspot temperature<br />

• Moisture c<strong>on</strong>tent in winding insulating paper<br />

• Moisture c<strong>on</strong>tent in barrier insulati<strong>on</strong><br />

• Relative ageing of the transformer insulati<strong>on</strong> system taking into account<br />

winding hotspot temperature and moisture c<strong>on</strong>tent in winding insulating<br />

paper.<br />

• Bubble incepti<strong>on</strong> temperature<br />

• Cooling system status<br />

• OLTC Tap positi<strong>on</strong> tracking (when equipped with OLTC)<br />

• OLTC temperature differential modeling (when equipped with external<br />

type OLTC)<br />

2.0 SCOPE of WORK:<br />

This is as a part of transformer supply, the transformer manufacturer shall also include<br />

in the scope of this tender, to supply, provisi<strong>on</strong>, mounting, erecti<strong>on</strong>, commissi<strong>on</strong>ing, etc;<br />

but not limited to the following, for <strong>on</strong> <strong>line</strong> moisture and gas in oil analyzer system.<br />