GETCO/E/TS – XMER01power/R4 Sept <strong>08</strong><br />

collecti<strong>on</strong> oil samples for DGA and moisture analysis, without disturbing IED or<br />

its c<strong>on</strong>necti<strong>on</strong>s. It shall be possible to carry out the periodic maintenance easily.<br />

The normal functi<strong>on</strong>ing of IED shall be guaranteed without necessity of any<br />

additives / c<strong>on</strong>sumable. The IED shall include an automatic 'self-test'<br />

feature which shall test the sensor and system twice per m<strong>on</strong>th. It shall<br />

include a dedicated "Fail Alarm" relay, should the test result in detecti<strong>on</strong><br />

of a problem in the sensor and/or system.<br />

Each IED shall be provided with multi <strong>line</strong> LCD with back light or red LED display<br />

to indicate combined gas c<strong>on</strong>centrati<strong>on</strong> level in ppm, moisture c<strong>on</strong>tent in RH% &<br />

ppm; hourly and daily trend readings, alarm etc. Key pad shall be built in for<br />

menu driven easy operati<strong>on</strong>. It shall be possible to down load all informati<strong>on</strong><br />

locally by a laptop computer. All the informati<strong>on</strong> shall also be c<strong>on</strong>tinuously<br />

transmitted to centralized m<strong>on</strong>itoring GETCO system. Necessary serial<br />

interfaces shall be provided. Minimum Four (4) nos. of potential free c<strong>on</strong>tacts<br />

and 4-20 mA analog output shall also be provided. The IED shall be<br />

electromagnetically screened and impervious to vibrati<strong>on</strong>s.<br />

3.2 Centralised M<strong>on</strong>itoring System:<br />

The centralised m<strong>on</strong>itoring system shall be installed in GETCO server for<br />

c<strong>on</strong>tinuous display recording and archiving of informati<strong>on</strong> received from all IEDs<br />

with a provisi<strong>on</strong> for receiving informati<strong>on</strong> from future IEDs also. The soft ware<br />

shall have menu driven pass word protected real time operating system with selfdiagnostic<br />

feature. The soft ware shall be suitable for graphical display of gas<br />

evoluti<strong>on</strong> and moisture level with daily and hourly trending as well as historical<br />

data and event recording. It shall be required to obtain audio visual alarm with<br />

suitable multiple thresholds for dissolved gas and moisture level ‘HIGH’, “HIGH -<br />

HIGH”, ‘FAIL’. It shall also possible to c<strong>on</strong>figure the IEDs from the centralizing<br />

system as well as local.<br />

3.3 Interc<strong>on</strong>necting Cabling:<br />

Glass Fiber Optic m<strong>on</strong>o mode cables /RS485 cable shall be provided for<br />

interc<strong>on</strong>necti<strong>on</strong> of all IEDs and the central m<strong>on</strong>itoring system. The cable shall be<br />

laid in HDPE c<strong>on</strong>duits. All required terminati<strong>on</strong>s, splicing kits shall be arranged<br />

by bidder. Provisi<strong>on</strong> shall be kept for installing and terminating cables from<br />

future IEDs.<br />

It is also intent to m<strong>on</strong>itor moisture and gas in oil of transformer through internet.<br />

There will not be any wire c<strong>on</strong>necti<strong>on</strong>. It will be wireless communicati<strong>on</strong>. Any<br />

suitable modem shall be provided. Data is to be seen and analyze at corporate<br />

office or any other remote locati<strong>on</strong>s as desired by GETCO.<br />

4.0 The <strong>on</strong> <strong>line</strong> moisture and gas in oil analyzer system shall be compatible to<br />

SCADA. It shall use DNP3.0 or Modbus protocol, without the use of third<br />

party protocol c<strong>on</strong>verters.<br />

Sign and Seal of Bidder Page 74 of 87