GETCO/E/TS – XMER01power/R4 Sept <strong>08</strong><br />

(h)<br />

(i)<br />

(j)<br />

Butterfly valves / Gate valves <strong>on</strong> oil drain pipe and nitrogen injecti<strong>on</strong> pipe which<br />

should be able to withstand full vacuum.<br />

Supports, signal box etc. which are to be painted with enameled paint.<br />

Any other item required for satisfactory operati<strong>on</strong> of system.<br />

Power supply<br />

For C<strong>on</strong>trol Box<br />

For FEC Auxiliary<br />

<str<strong>on</strong>g>220</str<strong>on</strong>g> V / 110 V DC<br />

230 V AC<br />

Spares for three (3) years Operati<strong>on</strong> & Maintenance<br />

The bidder apart from the below menti<strong>on</strong>ed spares shall submit a list of recommendati<strong>on</strong><br />

spares for three years trouble free operati<strong>on</strong> of the equipments and also furnish unit rates.<br />

The owners will scrutinize the said list and decide <strong>on</strong> the items <strong>on</strong> spares to be ordered<br />

and the quantities. These spares shall be supplied by the c<strong>on</strong>tractor before end of<br />

guarantee period. The owner reserves right to order the spares with twelve (12) m<strong>on</strong>ths<br />

from the date of order for main equipments and the rate shall be kept valid till this date.<br />

The prices of these spares shall not be c<strong>on</strong>sidered for evaluati<strong>on</strong> of the bid.<br />

Mandatory Spares<br />

Cylinder filled with Nitrogen of required<br />

Capacity per substati<strong>on</strong>.<br />

Detectors per transformer<br />

1 No.<br />

3 No.<br />

Regulator assembly per sub-stati<strong>on</strong><br />

1 No.<br />

Modificati<strong>on</strong> <strong>on</strong> the transformer<br />

No modificati<strong>on</strong> <strong>on</strong> the transformer shall be allowed which affects its performance (i.e.<br />

efficiency, losses, heat dissipati<strong>on</strong> ability etc.) safety, life etc. or it’s any other useful<br />

parameter. This requirement shall be paramount importance and shall form the essence<br />

of the c<strong>on</strong>tract.<br />

However, in any case, performance of transformer should not be affected in any manner<br />

by having Nitrogen Injecti<strong>on</strong> Fire Preventi<strong>on</strong> Cum Extinguishing System (NIFPES) and<br />

the C<strong>on</strong>tractor / Sub-C<strong>on</strong>tractor shall give an undertaking to this effect. All pipes should<br />

be washed / rinsed with transformer oil. If any damage is d<strong>on</strong>e to the transformer and /<br />