GETCO/E/TS – XMER01power/R4 Sept <strong>08</strong><br />

50 MVA 100 MVA<br />

(a) Type 3 phase two winding transformer<br />

(b) Rated capacity 25/35/50 MVA 50/70/100 MVA<br />

(c) Rated voltage <str<strong>on</strong>g>220</str<strong>on</strong>g>/<str<strong>on</strong>g>66</str<strong>on</strong>g> KV<br />

(d) Highest system voltage (kV) 245/72.5 KV<br />

(e) System frequency (Hz) 50 Hz<br />

(f) Type of cooling ONAN/ONAF/OFAF<br />

(g) Vector Group YnYnO (Star/star)<br />

(h) System of grounding Solidly grounded<br />

(i)<br />

Insulati<strong>on</strong> level<br />

(a) 1.2/50 microsec<strong>on</strong>d impulse<br />

withstand (kV Peak)<br />

(b) Power frequency withstand (kV)<br />

(HV LV NEUTRAL)<br />

1050 350 170<br />

460 160 75<br />

(j) % Impedance 15%<br />

(k) Tapping range - 5 to + 15% in equal 16 steps each 1.25%<br />

<strong>on</strong> LV neutral end for LV variati<strong>on</strong>.<br />

(l) Type of tap changers ON LOAD TAP CHANGER (Resistance<br />

transiti<strong>on</strong> type)<br />

(m) C<strong>on</strong>necti<strong>on</strong> YnYnO (Star/star)<br />

(n) Short circuit level for the system KV KVA<br />

<str<strong>on</strong>g>220</str<strong>on</strong>g> 15300<br />

<str<strong>on</strong>g>66</str<strong>on</strong>g> 4573<br />

(o) System Fault level HV: 40 kA 3 sec<br />

(p)<br />

Minimum creepage distance for<br />

bushing (mm)<br />

<str<strong>on</strong>g>220</str<strong>on</strong>g> kV<br />

<str<strong>on</strong>g>66</str<strong>on</strong>g> kV<br />

36 kV<br />

LV: 25 kA 3 sec<br />

6125<br />

1815<br />

900<br />

(q) Service Outdoor Outdoor<br />

(r) Duty C<strong>on</strong>tinuous C<strong>on</strong>tinuous<br />

(s) Overload capacity As per IS:<str<strong>on</strong>g>66</str<strong>on</strong>g>00 – 1972 / IEC354<br />

(t) Partial Discharge level 500 pico-columb 500 pico-columb<br />

2.3.2 The equipment offered shall be suitable for c<strong>on</strong>tinuous operati<strong>on</strong> under the above<br />

c<strong>on</strong>diti<strong>on</strong>s at the full rated capacity.<br />

2.3.4 The power transformers shall in general have c<strong>on</strong>stant ohmic impedance between<br />

HV and LV <strong>on</strong> all taps. However, in case of parallel operati<strong>on</strong> with the existing<br />

transformer,<br />

Sign and Seal of Bidder Page 41 of 87