GETCO/E/TS – XMER01power/R4 Sept <strong>08</strong><br />
• Detector trip<br />
• Buchholz relay trip<br />
• Oil drain valve open<br />
• Extincti<strong>on</strong> in progress<br />
• Cylinder pressure low<br />
• Differential relay trip<br />
• PRV / RPRR trip<br />
• Transformer / reactor trip<br />
• System out of service<br />
• Fault in cable c<strong>on</strong>necting fault detector<br />
• Fault in cable c<strong>on</strong>necting differential relay<br />
• Fault in cable c<strong>on</strong>necting Buchholz relay<br />
• Fault in cable c<strong>on</strong>necting PRV / RPRR<br />
• Fault in cable c<strong>on</strong>necting transformer reactor trip<br />
• Fault in cable c<strong>on</strong>necting TCIV<br />
• Auto / Manual / Off<br />
• Extincti<strong>on</strong> release <strong>on</strong> / off<br />
• Lamp test<br />
• Visual / Audio alarm for AC supply fail<br />
• Visual / Audio alarm for DC supply fail<br />
As far as possible the c<strong>on</strong>trol box should be such devised that all the transformers and<br />
reactors or group thereof should be c<strong>on</strong>trolled from single spot.<br />
Transformer C<strong>on</strong>servator Isolati<strong>on</strong> Valve.<br />
Transformer c<strong>on</strong>servator isolati<strong>on</strong> valve (TCIV) to be fitted in the c<strong>on</strong>servator pipe <strong>line</strong>,<br />
between c<strong>on</strong>servator and buchholz relay which shall operate for isolating the c<strong>on</strong>servator<br />
during abnormal flow of oil due to rupture / explosi<strong>on</strong> of tank or bursting of bushing.<br />
The valve shall not isolate c<strong>on</strong>servator during normal flow of oil during filtrati<strong>on</strong> or<br />
filling or refilling, locking plates to be provided with handle for pad locking. It shall<br />
have proximity switch for remote alarm, indicati<strong>on</strong> with visual positi<strong>on</strong> indicator.<br />
The TCIV should be of the best quality as malfuncti<strong>on</strong>ing of TCIV could lead to serious<br />
c<strong>on</strong>sequence. The closing of TCIV means stoppage of breathing of transformer / reactor.<br />
Locking plates shall be provided for pad locking.<br />
Detectors<br />
The system shall be complete with adequate number of detectors (quartz bulb) fitted <strong>on</strong><br />
the top cover of the transformer / reactor oil tank.<br />
Signal box<br />