GETCO/E/TS – XMER01power/R4 Sept <strong>08</strong><br />

• Detector trip<br />

• Buchholz relay trip<br />

• Oil drain valve open<br />

• Extincti<strong>on</strong> in progress<br />

• Cylinder pressure low<br />

• Differential relay trip<br />

• PRV / RPRR trip<br />

• Transformer / reactor trip<br />

• System out of service<br />

• Fault in cable c<strong>on</strong>necting fault detector<br />

• Fault in cable c<strong>on</strong>necting differential relay<br />

• Fault in cable c<strong>on</strong>necting Buchholz relay<br />

• Fault in cable c<strong>on</strong>necting PRV / RPRR<br />

• Fault in cable c<strong>on</strong>necting transformer reactor trip<br />

• Fault in cable c<strong>on</strong>necting TCIV<br />

• Auto / Manual / Off<br />

• Extincti<strong>on</strong> release <strong>on</strong> / off<br />

• Lamp test<br />

• Visual / Audio alarm for AC supply fail<br />

• Visual / Audio alarm for DC supply fail<br />

As far as possible the c<strong>on</strong>trol box should be such devised that all the transformers and<br />

reactors or group thereof should be c<strong>on</strong>trolled from single spot.<br />

Transformer C<strong>on</strong>servator Isolati<strong>on</strong> Valve.<br />

Transformer c<strong>on</strong>servator isolati<strong>on</strong> valve (TCIV) to be fitted in the c<strong>on</strong>servator pipe <strong>line</strong>,<br />

between c<strong>on</strong>servator and buchholz relay which shall operate for isolating the c<strong>on</strong>servator<br />

during abnormal flow of oil due to rupture / explosi<strong>on</strong> of tank or bursting of bushing.<br />

The valve shall not isolate c<strong>on</strong>servator during normal flow of oil during filtrati<strong>on</strong> or<br />

filling or refilling, locking plates to be provided with handle for pad locking. It shall<br />

have proximity switch for remote alarm, indicati<strong>on</strong> with visual positi<strong>on</strong> indicator.<br />

The TCIV should be of the best quality as malfuncti<strong>on</strong>ing of TCIV could lead to serious<br />

c<strong>on</strong>sequence. The closing of TCIV means stoppage of breathing of transformer / reactor.<br />

Locking plates shall be provided for pad locking.<br />

Detectors<br />

The system shall be complete with adequate number of detectors (quartz bulb) fitted <strong>on</strong><br />

the top cover of the transformer / reactor oil tank.<br />

Signal box<br />