Configuration 55/119<br />

Figure 29: STEP7 Signal Configuration (Example)<br />

PDI Editor Table Meaning Range of<br />

Value/ Value<br />

Tree Structure<br />

Shows the structure of the „Devices“, „Modules“ and „Signals“.<br />

Symbol Symbol for „Device“ = , „Module“ = or „Signal“ =<br />

Name<br />

Station<br />

Address<br />

Editable name for the „Devices“, „Modules“ and „Signals“:<br />

With STEP7 import the names of the STEP7 program, of the symbol table<br />

or of the data block and the signal are displayed. Without import the default<br />

names Device, Module, Signal are displayed.<br />

(only for PLC address of the <strong>PROFIBUS</strong> <strong>MPI</strong> device<br />

devices)<br />

Important! Here the PLC station address must be<br />

entered. The station address of the STEP7 project<br />

may not be used here.<br />

1 … 126<br />

Module Type<br />

(only for<br />

modules)<br />

Module type Symbol Table: The STEP7 symbol table is<br />

used. The S7 memory areas are valid.<br />

Module type Data Block: The data blocks DB1, DB2 … are<br />

used. The memory areas of the data blocks are valid.<br />

Symbol Table,<br />

Data Block<br />

Data Block<br />

Number<br />

(only for<br />

modules)<br />

Number of the data block,<br />

(only editable if „Module Type“ = Data Block)<br />

Signal Type<br />

(only for<br />

signals)<br />

Indicates, if the OPC client can „read“, „write“ or „read/write“<br />

the value of the signal..<br />

read,<br />

write,<br />

read_write<br />

Memory area<br />

(only for<br />

signals)<br />

Memory areas of the PLC (S7);<br />

(can only be selected, if „Module Type“ = Symbol Table)<br />

Selectable memory areas:<br />

I = Input<br />

Q = Output<br />

M = Merker<br />

C = Counter<br />

T = Timer<br />

I, Q, M, C, T<br />

Data Type<br />

(only for<br />

signals)<br />

Option for the data type of a signal. For the data type bit also<br />

the Bit-Number must be selected.<br />

Details on the STEP7 data types are listed in section STEP7<br />

Data Types page 61.<br />

bit, byte, word,<br />

signed16, dword,<br />

signed32, real32,<br />

string<br />

<strong>DTM</strong> for Hilscher <strong>PROFIBUS</strong> <strong>MPI</strong> Devices | Configuration of Hilscher <strong>MPI</strong> Devices<br />