CHAPTER 6 COMMUNICATION FUNCTION<br />

3) Parameter setting and modification<br />

If you double click the relevant parameter in the parameter setting basic screen of the<br />

Figure, the high speed link parameter setting screen will appear.<br />

parameter setting initial screen<br />

● Area : to set the reading area of the data to send when sending, and the saving area of<br />

the received data when receiving.<br />

● Size : the size of data for sending/receiving. The unit is 1byte and it is available to set<br />

Point<br />

1kbyte for total sending/receiving G3/4/6L-PUEA and 7kbytes for G3/4/6L-PUEB.<br />

1) The size of sending area and receiving area is total no. of I/O contact that created<br />

in SyCon.<br />

2) G4L-PUEA 1EA, GPL-TR2A(16points), GPL-TR4A(32points), GPL-<br />

D22A(16points) in order and when setting the sending area by<br />

P000, receiving area by P010,<br />

* Sending area : P000<br />

* Receiving area : P010<br />

* Sending area size : 6 bytes(total output contact number)<br />

* Receiving area size : 2 bytes(total input contact number),<br />

* P000의 data -> output by GPL-TR2A<br />

* P001~P002 data -> output by GPL-TR4A<br />

* GPL-D22A input -> saved in P010.<br />

3) The created order in SyCon is prior to station no. and cable connection when<br />

sending/receiving the data.<br />

6-24