CHAPTER 6 COMMUNICATION FUNCTION<br />
Point<br />
1) The I/O contact size of sending area and receiving area should be set as the<br />
same as that of KGLWIN program and SyCon.<br />
When selecting Smart I/O module in SyCon, the sending/receiving area size of<br />
each module shall be set automatically.(available to verify in Slave Setting<br />
window.)<br />
2) G4L-PUEA 1EA and GPL-TR2A(16points), GPL-D22A(16points), GPL-RY2A<br />
(16points) are in order and when setting the sending area<br />
as %MW0, receiving area as %MW100,<br />
* Sending area : %MW0<br />
* Receiving area : %QW0.2.0<br />
* Sending area size : 4 bytes(total output contact number)<br />
* Receiving area size : 2 bytes(total input contact number)<br />
* %MW0 data -> output to GPL-TR2A<br />
* %MW1 data -> output to GPL-RY2A<br />
* GPL-D22A input -> saved in %QW0.2.0<br />
3) It doesn’t matter which one is set in advance between GMWIN program and<br />
SyCon.<br />
2) High speed link parameter setting in GM4(Station 0)<br />
• Master module GMWIN program<br />
6-42