CHAPTER 8 INSTALLATION AND STARTUP<br />

8.3.2 Regular Checking<br />

Check the following items once or twice within 6 months and take necessary actions as follows :<br />

Checking items Checking method Judgment criteria Action<br />

Temperature Measured by<br />

0~55 ℃ Adjust acc. to<br />

Humidity thermometer/humidifier 5~95 %RH general spec.<br />

(Ex: environment<br />

Surrounding<br />

standard inside<br />

environment<br />

Measure the corrosive<br />

Pollution<br />

No corrosive gas control panel if<br />

gas<br />

using it inside<br />

control panel)<br />

Loosening, Move the communication Strong<br />

Module shaking module.<br />

attachment<br />

Screw tightening<br />

state Dust, foreign<br />

Visual examination No attachment<br />

materials<br />

Terminal screw<br />

loosening<br />

Tightening by the driver No loosening Tightening<br />

Approach of<br />

Connection<br />

compressed<br />

state<br />

terminal<br />

Visual examination Proper interval Correction<br />

Connector<br />

Connector fixing<br />

Visual examination No loosening<br />

loosening<br />

screw tightening<br />

Power voltage check<br />

Measure the voltage<br />

AC 85~132VAC Change the<br />

between AC 110/220V<br />

170~264V supply power.<br />

terminal<br />

Table 8.4 Regular checking items<br />

8-7