CHAPTER 6 COMMUNICATION FUNCTION<br />
• Communication opening verification<br />
Online Start Communication Start Debug Mode<br />
Point<br />
1) The size of Sending area and receiving area is total I/O contact number in<br />
GMWIN.<br />
When setting GM7 slave in SyCon, the I/O contact number in slave setting should<br />
be the same as high speed link setting size of GMWIN program.<br />
2) G4L-PUEA 1EA and GM7-PBEA 1EA are in order and when setting the<br />
sending area of master as %MW0, receiving area as %MW100,<br />
* Sending area : %MW0<br />
* Receiving area : % QW0.4.0<br />
* Sending area size : 64 bytes<br />
* Receiving area size : 64 bytes,<br />
* %MW0 data -> output to GM7 Slave module<br />
* GM7 Slave module input -> saved in % QW0.4.0.<br />
3) When using GM7 as slave, set GMWIN program in advance and open the<br />
communication by SyCon.<br />