Power Engineering<br />

Class I+II+III (T1+T2+T3) Combined Arresters<br />

PowerPro BCD, TN-C, TN-S and TT Systems<br />

PowerPro BCD TT2+1<br />

Combined modular multi-pole arrester for 2-phase TT systems.<br />

• Optional remote signalling contact (FM)<br />

L1 L1' L2 L2'<br />

PE<br />

PE'<br />

Patented<br />

Patented<br />

n<br />

n<br />

11 12<br />

11 12<br />

11 12<br />

N N N<br />

Basic circuit diagram<br />

Technical Data PP BCD TT2+1 25/100<br />

Nominal alternating voltage (UN) 230/400 V~<br />

Max. continuous operating alternating voltage (Uc) 255 V~<br />

Insulation resistance (Risol)<br />

>10 GΩ<br />

Protection level at 100% lightn. imp. sparkover voltage (1.2/50 µs) (Uas) ≤ 1.0 kV<br />

Protection level at Iimp (10/350 µs) [L-N] (Up)<br />

≤ 1.0 kV<br />

Response time (tA)<br />

< 50 ns<br />

Lightning impulse current (10/350 µs) [L1+L2+N-PE] (Itotal)<br />

100 kA<br />

Lightning impulse current (10/350 µs) [L-N] Iimp<br />

25 kA<br />

Lightning impulse current (10/350 µs) [N-PE] Iimp<br />

100 kA<br />

Follow-on current extinguishing capability at Uc (50/60 Hz) (Ifi) 4 kA<br />

Nominal discharge current (8/20 µs) (In)<br />

100 kA<br />

Short-circuit withstand capability at max. back-up fuse (Ik)<br />

50 kA<br />

Max. acceptable fuse or back-up fuse F2 (spur wiring)<br />

250 A gL/gG A<br />

Max. acceptable fuse or back-up fuse F1 (V-wiring)<br />

125 A gL/gG A<br />

Operating temperature range (TU) -40 – +80 °C<br />

Max. conductor cross section<br />

50 mm² stranded / 35 mm² fine-stranded<br />

Recommended conductor cross section<br />

25 mm²<br />

Max. connection torque for terminals<br />

4.5 Nm<br />

Enclosure material / colour<br />

polycarbonate (halogen-free) UL94-V0 / yellow<br />

Degree of protection (IEC EN 60529) IP 20<br />

Order Data<br />

Product PP BCD TT2+1 25/100<br />

Ordering part no. 37 39 34<br />

Technical Data and Order Data<br />

PP BCD TT2+1 25/100/FM<br />

FM contact / contact type<br />

break contact<br />

Switching capacity<br />

250 V/2 A<br />

Product<br />

PP BCD TT2+1 25/100/FM<br />

Ordering part no. 37 39 36<br />