Power Engineering<br />
Class I+II+III (T1+T2+T3) Combined Arresters<br />
PowerPro BCD, TN-C, TN-S and TT Systems<br />
PowerPro BCD TT2+1<br />
Combined modular multi-pole arrester for 2-phase TT systems.<br />
• Optional remote signalling contact (FM)<br />
L1 L1' L2 L2'<br />
PE<br />
PE'<br />
Patented<br />
Patented<br />
n<br />
n<br />
11 12<br />
11 12<br />
11 12<br />
N N N<br />
Basic circuit diagram<br />
Technical Data PP BCD TT2+1 25/100<br />
Nominal alternating voltage (UN) 230/400 V~<br />
Max. continuous operating alternating voltage (Uc) 255 V~<br />
Insulation resistance (Risol)<br />
>10 GΩ<br />
Protection level at 100% lightn. imp. sparkover voltage (1.2/50 µs) (Uas) ≤ 1.0 kV<br />
Protection level at Iimp (10/350 µs) [L-N] (Up)<br />
≤ 1.0 kV<br />
Response time (tA)<br />
< 50 ns<br />
Lightning impulse current (10/350 µs) [L1+L2+N-PE] (Itotal)<br />
100 kA<br />
Lightning impulse current (10/350 µs) [L-N] Iimp<br />
25 kA<br />
Lightning impulse current (10/350 µs) [N-PE] Iimp<br />
100 kA<br />
Follow-on current extinguishing capability at Uc (50/60 Hz) (Ifi) 4 kA<br />
Nominal discharge current (8/20 µs) (In)<br />
100 kA<br />
Short-circuit withstand capability at max. back-up fuse (Ik)<br />
50 kA<br />
Max. acceptable fuse or back-up fuse F2 (spur wiring)<br />
250 A gL/gG A<br />
Max. acceptable fuse or back-up fuse F1 (V-wiring)<br />
125 A gL/gG A<br />
Operating temperature range (TU) -40 – +80 °C<br />
Max. conductor cross section<br />
50 mm² stranded / 35 mm² fine-stranded<br />
Recommended conductor cross section<br />
25 mm²<br />
Max. connection torque for terminals<br />
4.5 Nm<br />
Enclosure material / colour<br />
polycarbonate (halogen-free) UL94-V0 / yellow<br />
Degree of protection (IEC EN 60529) IP 20<br />
Order Data<br />
Product PP BCD TT2+1 25/100<br />
Ordering part no. 37 39 34<br />
Technical Data and Order Data<br />
PP BCD TT2+1 25/100/FM<br />
FM contact / contact type<br />
break contact<br />
Switching capacity<br />
250 V/2 A<br />
Product<br />
PP BCD TT2+1 25/100/FM<br />
Ordering part no. 37 39 36<br />