Power Engineering<br />
Class II (T2) Surge Arresters, leakage-current free<br />
EnerPro C, TN-C, TN-S and TT Systems<br />
• Monitoring of conductor and arrester via LED<br />
• With multi-functional terminals, max. 35 mm²<br />
• Compact housing, no contact problems with plug-in<br />
connections<br />
• Class II SPD on the basis of hermetically sealed raregas-filled<br />
spark gaps<br />
• Possible to coordinate with upstream installed<br />
<strong>Leutron</strong> lightning current arresters of classes I, I+II<br />
and I+II+III<br />
• Leakage-current free version to protect the foundation<br />
earthing electrode against ac-caused corrosion<br />
• Optional remote signalling contact (FM) requiring no<br />
additional space<br />
Multi-pole surge arresters for the protection of low-voltage<br />
consumers’ installations in industry, business and residential<br />
areas against transient surges caused by lightning (LEMP) or<br />
switching actions in the network (SEMP).<br />
The arresters can be installed at the transition 0 B to 1 and<br />
higher, according to the lightning protection zones concept.<br />
The multi-pole complete units in compact housings are available<br />
for TN-C, TN-S, TN-C-S and TT systems as well as for threephase<br />
systems according to IEC (EN, VDE, OEVE, etc.) standards.<br />
They are shipped ready-to-connect.<br />
With their leakage current-free design, TOV security and LED<br />
monitoring as well as their optional hermetically-sealed remote<br />
alarm contacts the arresters set new standards in terms<br />
of monitoring comfort, security, reliability and life expectancy.<br />
The arresters can be combined with upstream installed<br />
arresters of the series PowerPro and IsoPro.<br />
The SPD modules have thermal disconnection devices per<br />
pole, which respond if, due to an overload, the partial lightning<br />
current through the metal oxide varistor exceeds a certain<br />
value. In this case the green LED extinguishes and the optional<br />
thermal sensor with remote contact (normally closed)<br />
opens. In order to maintain the surge voltage protection the<br />
SPD has to be replaced immediately.<br />
The thermally triggered, potential-free remote alarm contact<br />
is a hermetically sealed switch to eliminate environmental<br />
influences and to guarantee the highest possible security.<br />
For security reasons it is designed as a normally closed contact<br />
(NC).<br />
The MOV and the expulsion-type spark gap are connected<br />
in series to avoid heating and, thus, ageing in the state of<br />
rest. Therefore, a considerable increase in life expectancy is<br />
reached. There is no need for expensive thermo sensors to<br />
monitor the surface temperature. Thus, the protection modules<br />
do not need to be pluggable<br />
The SPD is equipped with a reliable LED function display.<br />
The LED has a dual function as indicator for the varistor function<br />
and as voltage monitor. Therefore, a proper connection<br />
and function of the SPD is indicated during installation. Additionally,<br />
an extinguished LED during operation indicates a<br />
malfunction.<br />
Since this version is leakage current-free, the earthing system<br />
is protected against dangerous ac-caused corrosion and the<br />
earth leakage circuit-breaker will not be activated by leakage<br />
currents.<br />
Versions with additional gas-discharge spark gaps do not<br />
interfere with the function of permanently installed insulation<br />
monitoring devices and earth leakage circuit-breakers.<br />
The EP C units are also available with a rated voltage of 350<br />
V for a higher TOV resistance.<br />
In 230 V ac networks the optional potential-free remote contact<br />
(FM) can be updated by an additional acoustic/optical<br />
signalling device UAS 230-Tr with test key (Item no. 35 10 30),<br />
even at a later point in time.<br />
76 <strong>Leutron</strong> <strong>GmbH</strong> · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de