Power Engineering<br />

Class II (T2) Surge Arresters, leakage-current free<br />

EnerPro 280Tr<br />

EnerPro 280Tr<br />

Slim and Leakage-current free 2-pole surge arrester, e.g. for a 1-phase<br />

TN system. Only 1 MW according to DIN 43880.<br />

• Optional remote signalling contact (PK)<br />

• Monitoring of conductor and arrester<br />

Technical Data<br />

EnerPro 280Tr<br />

Nominal alternating voltage (UN) 230/400 V~<br />

Max. continuous direct voltage (Uc)<br />

275/480 V<br />

Max. acceptable fuse or back-up fuse<br />

125 A gL/gG A<br />

Protection level at 5 kA (Up)<br />

≤ 1.0 kV<br />

Protection level at In {L(N)-PE} (Urest)<br />

≤ 1.4 kV<br />

Response time (tA)<br />

≤ 50 ns<br />

Nominal discharge current (8/20 µs) {L(N)-PE} (In)<br />

15 kA<br />

Critical discharge current (8/20 µs) (Imax)<br />

18 kA<br />

Operating temperature range (TU) -40 – +80 °C<br />

Enclosure material / colour<br />

polycarbonate (halogen-free) UL94-V0 / yellow<br />

Casting compound<br />

polyurethane<br />

Mounting on 35 mm DIN rail (DIN EN 50 022)<br />

Net weight / pc<br />

110 g<br />

Basic circuit diagram<br />

Order Data<br />

Product<br />

EnerPro 280Tr<br />

Ordering part no. 38 20 28<br />

Technical Data and Order Data<br />

EnerPro 280Tr/Pk<br />

FM contact / contact type<br />

break contact<br />

Switching capacity<br />

250 V/2 A<br />

Product<br />

EnerPro 280Tr/Pk<br />

Ordering part no. 38 20 29<br />

<strong>Leutron</strong> <strong>GmbH</strong> · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de<br />