Part - Leutron GmbH
Part - Leutron GmbH
Part - Leutron GmbH
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Power Engineering<br />
Class I+II (T1+T2) Combined Arresters<br />
PowerPro BC, TN-C, TN-S and TT Systems<br />
PowerPro BC TNC 440<br />
Combined modular multi-pole arrester for 3-phase TN-C systems with<br />
400/690 V.<br />
• Optional remote signalling contact (FM)<br />
L1 L1' L2 L2' L3 L3'<br />
Patented<br />
Patented<br />
Patented<br />
n<br />
n<br />
n<br />
PEN<br />
11 12<br />
PEN<br />
11 12<br />
PEN<br />
11 12<br />
Basic circuit diagram<br />
Technical Data PP BC TNC 440<br />
Nominal alternating voltage (UN) 400/690 V~<br />
Max. continuous operating alternating voltage (Uc) 440 V~<br />
Insulation resistance (Risol)<br />
>10 GΩ<br />
Protection level at 100% lightn. imp. sparkover voltage (1.2/50 µs) (Uas) ≤ 2.0 kV<br />
Protection level at Iimp (10/350 µs) [L-PE] (Up)<br />
≤ 2.0 kV<br />
Response time (tA)<br />