Power Engineering<br />

Class I+II (T1+T2) Combined Arresters<br />

IsoPro BC, TN-C, TN-S and TT Systems<br />

• Completely mounted on busbar, ready-to-connect<br />

• Discharge capacity up to 100 kA (10/350 µs)<br />

• High insulation resistance<br />

• Protection level ≤ 2 kV<br />

• V-wiring with multi-functional terminals<br />

• On the basis of hermetically sealed rare-gas-filled<br />

spark gaps<br />

• No blow-out vents, thus, not requiring any safety<br />

clearance to other installations<br />

• No leakage currents, thus, allowing installation<br />

upstream of power meters<br />

• Optional remote signalling contact (FM) requiring no<br />

additional space<br />

Multi-pole combined modular arresters for the protection of<br />

low-voltage consumers’ installations in industrial, business<br />

and residential areas against surges caused by lightning or<br />

switching actions in the network.<br />

The arresters can be installed at the transition 0 A to 2 according<br />

to the lightning protection zones concept.<br />

The series IsoPro (IP) is based on a well-proved technology.<br />

Per pole two selectively responding protection stages are<br />

placed in a combined DIN housing (2 MW of only 35 mm). The<br />

leakage current-free protective circuit consists of a varistor<br />

(MOV) and a gas-filled surge arrester (GDT) connected in series.<br />

In addition, a rare-gas-filled, hermetically sealed highperformance<br />

isolating spark gap from industrial ceramics<br />

– resistant against pressure and high temperatures – is connected<br />

in parallel.<br />

The IsoPro BC combined modular arrester is available with a<br />

discharge capability of 25 kA and 60 kA (10/350 µs) per pole,<br />

or at TT systems with 100 kA (10/350µs) between N and PE.<br />

Due to the application of the gas discharge technology the<br />

IsoPro BC SPDs are resistant against temporary and long lasting<br />

overvoltages (TOV) up to 500 V (50 Hz).<br />

Therefore, the SPDs of the series IsoPro can confidentially<br />

be applied at all protection levels according to DIN EN 62305<br />

(VDE 0185-305).<br />

This SPD has a redundant function. In case of a (theoretically<br />

possible) malfunction of the first protection stage the robust<br />

and overload-resistant main spark gap remains in operation<br />

and guarantees the coarse protection of the network.<br />

High-energy lightning impulse currents cause the main spark<br />

gap to fire, thus, protecting the first protection stage (MOV<br />

and GDT) against thermal overload.<br />

Only the first protection stage responds during occurring<br />

transient surges of low energy. The main spark gap will not<br />

fire. Due to the limiting behaviour of the MOV varistor the response<br />

of the first protection stage will not result in a short<br />

circuit and, therefore, in no follow-on short-circuit current.<br />

The back-up fuse will not actuate in this case.<br />

The main spark gap extinguishes follow-on short-circuit currents<br />

only under certain conditions. If a maximum operational<br />

availability is desired, a back-up fuse of ≤ 160 A is necessary<br />

to extinguish a firing main spark gap and, thus, preventing<br />

it from thermal damage. In most cases a back-up fuse will<br />

be installed in industrial applications and for maintenance<br />

reasons, whereby the power supply will not be interrupted<br />

even if the SPD fails.<br />

Lightning impulse currents with a high energy content cause<br />

the main spark gap to fire immediately after the triggering<br />

of the first protection stage. Hence, the main spark gap with<br />

its discharge capacity unloads the first stage and protects it<br />

against damage.<br />

With back-up fuses or circuit-breakers of more than 160 A a<br />

selective back-up fuse (fusible cutout) of a maximum of 160 A<br />

has to be installed to avoid an overload of the IsoPro caused<br />

by a high short-circuit current.<br />

Combined modular arresters of the series BC offer a higher<br />

insulation level and lower investment and installation costs,<br />

due to their low residual voltage. They are able to divert high<br />

lightning impulse currents and operate also at small, transient<br />