Power Engineering<br />
Class I (T1) Lightning Current Arresters<br />
IsoPro B, 2-pole<br />
• All-in-one modular protection unit, ready for connection<br />
• Discharge capacity up to 100 kA (10/350µs)<br />
• Maximum operational availability<br />
• Rare-gas-filled spark gap, hermetically sealed<br />
• Operates independently of atmospheric air pressure<br />
and ambient humidity<br />
• Protection level = 4 kV<br />
• V-wiring with multi-functional terminals<br />
• High TOV resistance<br />
• High insulation resistance<br />
• No blow-out vents, thus, not requiring any safety<br />
clearance to other installations<br />
• No leakage currents, thus, allowing installation<br />
upstream of power meters<br />
• Optional remote signalling contact (FM) requiring no<br />
additional space<br />
Two-pole lightning current arresters for the protection of<br />
low-voltage consumers’ installations in industry, business and<br />
residential areas against transient surges caused by switching<br />
actions or lightning.<br />
The arresters can be installed at the transition 0 A to 1 according<br />
to the lightning protection zones concept.<br />
The single-phase (2-pole) IsoPro series is subdivided into the<br />
following performance groups and voltage protection levels:<br />
• 25 kA and 60 kA (10/350 µs) per active conductor or, at TT<br />
systems, between N and PE 100 kA (10/350 µs), and between<br />
the active conductors and PE or N, therefore in total:<br />
50 kA or 100 kA.<br />
• It is classified as class I (T1) SPD (former category B) with<br />
a voltage protection level of 4 kV depending on the impulse<br />
current load.<br />
The series IsoPro (IP) is based on a well-proved technology.<br />
Per pole two selectively responding protection stages are<br />
placed in a combined DIN housing (2 MW of only 35 mm). The<br />
leakage current-free protective circuit consists of a varistor<br />
(MOV) and a gas-filled surge arrester (GDT) connected in series.<br />
In addition, a rare-gas-filled, hermetically sealed highperformance<br />
isolating spark gap from industrial ceramics<br />
– resistant against pressure and high temperatures – is connected<br />
in parallel.<br />
Therefore, the SPDs of the series IsoPro can confidentially<br />
be applied at all protection levels according to DIN EN 62305<br />
(VDE 0185-305).<br />
This SPD has a redundant function. In case of a (theoretically<br />
possible) malfunction of the first protection stage the robust<br />
and overload-resistant main spark gap remains in operation<br />
and guarantees the coarse protection of the network.<br />
In case of high-energy lightning impulse currents the main<br />
spark gap fires, thus, protecting the first protection stage<br />
(MOV and GDT) against thermal overload.<br />
Due to the application of the gas discharge technology in<br />
both protection stages, the IsoPro SPDs are resistant against<br />
temporary and long lasting overvoltages (TOV) up to 500 V<br />
(50 Hz).<br />
Only the first protection stage responds during occurring<br />
transient surges of low energy. The main spark gap will not<br />
fire. Due to the limiting behaviour of the MOV varistor the response<br />
of the first protection stage will not result in a short<br />
circuit and, therefore, in no follow-on short-circuit current.<br />
The back-up fuse will not actuate in this case.<br />
Lightning impulse currents with a high energy content cause<br />
the main spark gap to fire immediately after the triggering<br />
of the first protection stage. Hence, the main spark gap with<br />
its discharge capacity unloads the first stage and protects it<br />
against damage.<br />
With back-up fuses or circuit-breakers of more than 160 A a<br />
selective back-up fuse (fusible cutout) of a maximum of 160 A<br />
has to be installed to avoid an overload of the IsoPro caused<br />
by a high short-circuit current.<br />
<strong>Leutron</strong> <strong>GmbH</strong> · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de<br />