14.04.2014 Views

Part - Leutron GmbH

Part - Leutron GmbH

Part - Leutron GmbH

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Power Engineering<br />

Class II (T2) Surge Arresters, leakage-current free<br />

EnerPro C, TN-C, TN-S and TT Systems<br />

EnerPro C TT<br />

Compact and leakage-current free 4-pole surge arrester, e.g. for a 3-phase TT<br />

and TN-S system.<br />

• Optional remote signalling contact (FM)<br />

• Monitoring of conductor and arrester<br />

L1<br />

L2<br />

L3<br />

PE<br />

3<br />

Technical Data EP C TT 275 EP C TT 350<br />

N 11 12<br />

Nominal alternating voltage (UN) 230/400 V~ 230/400 – 240/415 V~<br />

Max. continuous operating alternating voltage (Uc) 275/480 V~ 350 V~<br />

Max. acceptable fuse or back-up fuse 125 A gL/gG A 125 A gL/gG A<br />

Protection level at 5 kA (Up) ≤ 1.0 kV ≤ 1.0 kV<br />

Protection level at In (Up) ≤ 1.4 kV ≤ 1.4 kV<br />

Response time (tA)

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!