Power Engineering<br />
Class I+II (T1+T2) Combined Arresters<br />
IsoPro BC, 2-pole<br />
• All-in-one modular protection unit, ready for<br />
connection<br />
• Discharge capacity up to 100 kA (10/350µs)<br />
• High insulation resistance<br />
• Protection level = 2 kV<br />
• V-wiring with multi-functional terminals<br />
• No leakage currents, thus, allowing installation<br />
upstream of power meters<br />
• On the basis of hermetically sealed rare-gas-filled<br />
spark gaps<br />
• No blow-out vents, thus, not requiring any safety<br />
clearance to other installations<br />
• Optional remote signalling contact (FM) requiring no<br />
additional space<br />
Two-pole combined arrester for the protection of low-voltage<br />
consumers’ installations in industry, business and residential<br />
areas against transient surges caused by lightning (LEMP) or<br />
switching actions in the network (SEMP).<br />
The arresters can be installed at the transition 0A to 2<br />
according to the lightning protection zones concept.<br />
The single-phase (2-pole) IsoPro series is subdivided into the<br />
following performance groups and voltage protection levels:<br />
• 25 kA and 60 kA (10/350 µs) per active conductor or, at TT<br />
systems, between N and PE 100 kA (10/350 µs), and between<br />
the active conductors and PE or N, therefore in<br />
total: 50 kA or 100 kA.<br />
• It is classified as class I+II (T1+T2) SPD (former category<br />
B+C) with a voltage protection level of 2 kV or < 2,5 kV<br />
depending on the impulse current load.<br />
All other features correspond to those of the multi-pole combined<br />
arresters.<br />
<strong>Leutron</strong> <strong>GmbH</strong> · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de<br />