Power Engineering<br />

Class II (T2) Surge Arresters, leakage-current free<br />

EnerPro C, TN-C, TN-S and TT Systems<br />

EnerPro C TNS<br />

Compact and leakage-current free 4-pole surge arrester, e.g. for a 3-phase<br />

TN-S system.<br />

• Optional remote signalling contact (FM)<br />

• Monitoring of conductor and arrester<br />

L1<br />

L2<br />

L3<br />

N<br />

4<br />

PE<br />

11 12<br />

FM<br />

Basic circuit diagram<br />

Technical Data EP C TNS 275 EP C TNS 350<br />

Nominal alternating voltage (UN) 230/400 V~ 350 V~<br />

Max. continuous operating alternating voltage (Uc) 275/480 V~ 275/480 V~<br />

Max. acceptable fuse or back-up fuse 125 A gL/gG A 125 A gL/gG A<br />

Protection level at 5 kA (Up) ≤ 1.0 kV ≤ 1.3 kV<br />

Protection level at In (8/20 µs) (Up) ≤ 1.4 kV ≤ 1.75 kV<br />

Response time (tA)