Power Engineering<br />

Class I+II (T1+T2) Combined Arresters<br />

surges under different ambient conditions without any additional<br />

trigger – reliably and without any problems.<br />

The SPDs are leakage-current free and protect the earthing<br />

system against dangerous ac-caused corrosion.<br />

Due to their good insulation against earth of 10 GΩ and the<br />

fact that no leakage-current affected varistors (MOV) are<br />

connected in parallel, they even can be placed upstream<br />

of the meter according to the specifications of the German<br />

VDN (TAB 2007).<br />

The modular designed, multi-pole complete units are available<br />

for TN, TN-C, TN-S, TN-C-S, and TT systems according to<br />

IEC (EN, VDE, OEVE, etc.) standards. They are shipped readyto-connect<br />

(on rail).<br />

<strong>Leutron</strong> also offers a special version with a higher operating<br />

voltage. The units can universally be installed at all export<br />

countries with nominal system voltages of 200 to 260 V.<br />

The TT system version discharges the impulse current between<br />

L and N. Between N and PE a <strong>Leutron</strong> summation current<br />

spark gap SumPro with 100 kA (10/350µs) will be applied<br />

which corresponds to the highest lightning protection class<br />

I according to VDE 0185-305 (IEC DIN EN 62305).<br />

The pre-assembled, two-pole busbars at the terminals allow<br />

a serial V-wiring of the SPD to a back-up fuse up to 125 A.<br />

In the case of single-pole units the individual SPD modules<br />

can optionally be delivered with integrated, non-resetable<br />

thermal sensors (/FM) or (/Pk).<br />

At an overload of the SPD the sensors open a hermeticallysealed,<br />

potential-free remote contact permanently.<br />

The sensors are already triggered before a possible damage<br />

of the SPD module, which then has to be replaced for security<br />

reasons.<br />

The remote contacts have to be included in the order of the<br />

SPD. Retrofitting is not possible.<br />

The remote signalling contact (FM or Pk) is connected via a<br />

twisted-pair cable to an integrated plug-type terminal block<br />

of the SPD.<br />

The latching hooks per pole on both sides of the SPD allow<br />

for an installation on a 35 mm DIN rail, even under difficult<br />

mounting conditions inside the distributor.<br />

For a supply from below, the labels can be reversed and the<br />

front plate can be turned through 180°. On demand, a second,<br />

self-adhesive front plate can be delivered as a replacement,<br />

free of charge.<br />

<strong>Leutron</strong> <strong>GmbH</strong> · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de<br />