Part - Leutron GmbH
Part - Leutron GmbH
Part - Leutron GmbH
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Power Engineering<br />
Class I+II (T1+T2) Combined Arresters<br />
surges under different ambient conditions without any additional<br />
trigger – reliably and without any problems.<br />
The SPDs are leakage-current free and protect the earthing<br />
system against dangerous ac-caused corrosion.<br />
Due to their good insulation against earth of 10 GΩ and the<br />
fact that no leakage-current affected varistors (MOV) are<br />
connected in parallel, they even can be placed upstream<br />
of the meter according to the specifications of the German<br />
VDN (TAB 2007).<br />
The modular designed, multi-pole complete units are available<br />
for TN, TN-C, TN-S, TN-C-S, and TT systems according to<br />
IEC (EN, VDE, OEVE, etc.) standards. They are shipped readyto-connect<br />
(on rail).<br />
<strong>Leutron</strong> also offers a special version with a higher operating<br />
voltage. The units can universally be installed at all export<br />
countries with nominal system voltages of 200 to 260 V.<br />
The TT system version discharges the impulse current between<br />
L and N. Between N and PE a <strong>Leutron</strong> summation current<br />
spark gap SumPro with 100 kA (10/350µs) will be applied<br />
which corresponds to the highest lightning protection class<br />
I according to VDE 0185-305 (IEC DIN EN 62305).<br />
The pre-assembled, two-pole busbars at the terminals allow<br />
a serial V-wiring of the SPD to a back-up fuse up to 125 A.<br />
In the case of single-pole units the individual SPD modules<br />
can optionally be delivered with integrated, non-resetable<br />
thermal sensors (/FM) or (/Pk).<br />
At an overload of the SPD the sensors open a hermeticallysealed,<br />
potential-free remote contact permanently.<br />
The sensors are already triggered before a possible damage<br />
of the SPD module, which then has to be replaced for security<br />
reasons.<br />
The remote contacts have to be included in the order of the<br />
SPD. Retrofitting is not possible.<br />
The remote signalling contact (FM or Pk) is connected via a<br />
twisted-pair cable to an integrated plug-type terminal block<br />
of the SPD.<br />
The latching hooks per pole on both sides of the SPD allow<br />
for an installation on a 35 mm DIN rail, even under difficult<br />
mounting conditions inside the distributor.<br />
For a supply from below, the labels can be reversed and the<br />
front plate can be turned through 180°. On demand, a second,<br />
self-adhesive front plate can be delivered as a replacement,<br />
free of charge.<br />
<strong>Leutron</strong> <strong>GmbH</strong> · Humboldtstrasse 30 · 70771 Leinfelden-Echterdingen · Germany · Phone +49 711 94771-0 · www.leutron.de<br />
45