Comments on Loading Combinations for ODE<br />

• The structure should first be designed with adequate strength capacity under static<br />

loading conditions.<br />

• For cut-and-cover tunnel structures, the evaluation <strong>of</strong> capacity using Equation 2-3<br />

should consider the uncertainties associated with the loads E1 and E2, and their worst<br />

combination. For mined circular tunnels (Equation 2-4), similar consideration should<br />

be given to the loads EX and H.<br />

When the extreme loads are used for design, a smaller load factor is recommended to<br />

avoid unnecessary conservatism. Note that an extreme load may be a maximum load<br />

or a minimum load, depending on the most critical case <strong>of</strong> the loading combinations.<br />

Use Equation 2-4 as an example. For a deep circular tunnel lining, it is very likely that<br />

the most critical loading condition occurs when the maximum excavation loading, EX,<br />

is combined with the minimum hydrostatic water pressure, H. For a cut-and-cover<br />

tunnel, the most critical seismic condition may <strong>of</strong>ten be found when the maximum<br />

lateral earth pressure, E2, is combined with the minimum vertical earth load, E1. If a<br />

very conservative lateral earth pressure coefficient is assumed in calculating the E2,<br />

the smaller load factor b 1 = 1.05 should be used.<br />

• Redistribution <strong>of</strong> moments (e.g., ACI 318) for cut-and-cover concrete frames is<br />

recommended to achieve a more efficient design.<br />

• If the “strength” criteria expressed by Equation 2-3 or 2-4 can be satisfied based on<br />

elastic structural analysis, no further provisions under the ODE are required.<br />

• If the flexural strength <strong>of</strong> the tunnel lining, using elastic analysis and Equation 2-3 or 2-<br />

4, is found to be exceeded, the structure should be checked for its ductility to ensure<br />

that the resulting inelastic deformations, if any, are small. If necessary, the structure<br />

should be redesigned to ensure the intended performance goals during the ODE.<br />

• Zero live load condition (i.e., L = 0) should also be evaluated in Equations 2-3 and 2-4.<br />

23