APPENDIX 11<br />

BACKFLOW PREVENTION REQUIREMENTS<br />

Policy:<br />

1. Public <strong>Water</strong> Systems<br />

All approved public water systems interconnected to GSWSA shall have a<br />

common gate valve <strong>and</strong>/or check valve between the systems.<br />

2. Commercial Customers<br />

All new commercial irrigation customers shall have an approved reduced pressure<br />

backflow preventer assembly. Maintenance <strong>and</strong> annual certification of the<br />

reduced pressure backflow preventer shall be the responsibility of the customer.<br />

Customers may for a monthly fee as outlined in the approved rate resolution<br />

contract GSWSA to maintain <strong>and</strong> annually inspect cross-connection device.<br />

<strong>Water</strong> service to a commercial customer less than 2” will have a dual check or a<br />

cross-connection device installed (double check or reduced pressure backflow<br />

presenter) based on the Letter of Intent <strong>and</strong> the degree of hazard.<br />

<strong>Water</strong> service to a commercial customer greater than 2” will have a crossconnection<br />

device installed (double check or reduced pressure backflow<br />

presenter) based on the Letter of Intent <strong>and</strong> degree of hazard.<br />

Customers may for a monthly fee as outlined in the approved rate resolution<br />

contract GSWSA to maintain <strong>and</strong> annually inspect cross-connection device.<br />

NOTE: The customer shall own <strong>and</strong> maintain the cross connection device.<br />

3. Fire line systems shall have a detector double check valve assembly regardless of<br />

size unless the degree of hazard requires a reduced pressure backflow preventer.<br />

Cross-connection control devices for fire suppression systems will be installed by<br />

GSWSA.<br />

4. The cost of providing <strong>and</strong> installing any cross-connection control devices shall be<br />

paid by the customer. The <strong>Authority</strong> shall maintain an up-to-date service charge<br />

schedule for installing cross-connection control devices in conjunction with the<br />

approved rate schedule.<br />

5. The GSWSA will maintain a current listing of all double check valve assemblies<br />

<strong>and</strong> RPBP device locations.<br />

<strong>Gr<strong>and</strong></strong> <strong>Str<strong>and</strong></strong> <strong>Water</strong> <strong>and</strong> <strong>Sewer</strong> <strong>Authority</strong> July 2009 Appendices<br />