Remarks of <strong>Siemens</strong><br />
This secti<strong>on</strong> outlines how <strong>Siemens</strong> interprets the functi<strong>on</strong>s and processing functi<strong>on</strong>s<br />
according to EN 15232:2012.<br />
5. The following main features distinguish TABS from other heating and cooling<br />
systems:<br />
- TABS is a low-temperature heating/high temperature cooling system<br />
- TABS activates relatively large thermal storage<br />
These features permit <strong>energy</strong>-efficient operati<strong>on</strong> in a number of cases<br />
6. As a rule, there is <strong>on</strong>ly a single flow temperature setpoint per z<strong>on</strong>e (heating<br />
and cooling – no setpoint range. This means: Frequently slight overheating<br />
or undercooling during transiti<strong>on</strong> periods (where heating and cooling are released).<br />
7. A setpoint range is used here; <strong>on</strong>e setpoint each can be preset separately<br />
for heating and cooling. This eliminates to some extent overheating or undercooling.<br />