Remarks of <strong>Siemens</strong><br />
This secti<strong>on</strong> outlines how <strong>Siemens</strong> interprets the functi<strong>on</strong>s and processing<br />
functi<strong>on</strong>s according to EN 15232:2012.<br />
7. If the ventilati<strong>on</strong> system serves <strong>on</strong>ly <strong>on</strong>e room and is c<strong>on</strong>trolled to the indoor<br />
temperature of that room, use "7.4 Heating and cooling c<strong>on</strong>trol", even if the<br />
c<strong>on</strong>trol acts <strong>on</strong> the supply temperature. In the other cases, the types of<br />
available c<strong>on</strong>trols must be differentiated.<br />
Exercise care when using this type of temperature c<strong>on</strong>trol, unless the<br />
system is designed to prevent simultaneous heating and cooling.<br />
8. An air washer that has a humidificati<strong>on</strong> <strong>efficiency</strong> of at least 95%, i.e. <strong>on</strong>e<br />
that can almost achieve the saturati<strong>on</strong> of the escaping air is required for<br />
dew point c<strong>on</strong>trol. If the temperature of this nearly saturated air is also c<strong>on</strong>trolled,<br />
its water vapor c<strong>on</strong>tent is fixed. Therefore, the required effort in<br />
terms of c<strong>on</strong>trol equipment is relatively small. This soluti<strong>on</strong> is appropriate in<br />
applicati<strong>on</strong>s where the air that has been cooled to the dew point is largely<br />
reheated by internal heat sources in the c<strong>on</strong>diti<strong>on</strong>ed space. If this is not the<br />
case, direct humidity c<strong>on</strong>trol is – for <strong>energy</strong> <strong>efficiency</strong> reas<strong>on</strong>s – preferable<br />
for c<strong>on</strong>venti<strong>on</strong>al air c<strong>on</strong>diti<strong>on</strong>ing systems.<br />
9. In the case of water spray humidificati<strong>on</strong>, a humidificati<strong>on</strong> <strong>efficiency</strong> that is<br />
c<strong>on</strong>siderably lower than that of the dewpoint air washer suffices. This<br />
means that a lower priced device can be used accordingly. It is, however,<br />
important for the humidifier to be c<strong>on</strong>trolled within a sufficiently large output<br />
range.<br />