02.01.2015 Views

Valent_IOM_Controls - RJI-Sales.com

Valent_IOM_Controls - RJI-Sales.com

Valent_IOM_Controls - RJI-Sales.com

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Setpoint Descriptors<br />

System<br />

Current Alarm<br />

Displays the current alarm state of the unit.<br />

View Only<br />

Reset<br />

This point allows the user to reset all of the units<br />

alarms and reboots the units controller. To reset the<br />

controller down arrow to the reset option, hit the<br />

enter button once, down arrow once to reset allow 5<br />

min, press enter again:<br />

Normal (default)<br />

Reset allow 5 min.<br />

Editable<br />

Occupancy<br />

Displays Occupied during the day (occupied hours),<br />

Unoccupied and night (unoccupied hours), and<br />

Standby (when unit is running in standby. The<br />

occupancy of the controller is determined by:<br />

• Hardwired occupancy input<br />

• Local time clock/schedule<br />

• Communicated <strong>com</strong>mand from building<br />

automation system<br />

When a hardwired occupancy input is used, remove<br />

the occupancy input jumper wire on Universal Input<br />

15. Connect the occupancy device to that input. The<br />

setup parameter for Occupancy Hardwired must be<br />

set to True.<br />

To use the units standby feature the Occupancy<br />

Hardwired must be left at false, occupied and<br />

unoccupied will be set via the units stand alone<br />

controller. When the stand alone schedule is occupied<br />

and the universal input 15 is open the unit will run in<br />

standby mode. When the stand alone schedule is<br />

occupied and the universal input 15 is closed the unit<br />

will run in occupied mode. When the stand alone<br />

schedule is unoccupied and the universal input 15 is<br />

either open or closed the unit will be in unoccupied<br />

mode.<br />

The occupancy can also be determined by the local<br />

time clock/schedule in the controller. When the local<br />

clock/schedule is used, set Occupancy Hardwired to<br />

False. Ensure that the time and date are set correctly<br />

in the controller.<br />

Finally, a <strong>com</strong>municated <strong>com</strong>mand from a building<br />

automation system (BAS) can be used to determine<br />

the occupancy of the controller. When a<br />

<strong>com</strong>municated <strong>com</strong>mand is to be used, set<br />

Occupancy Hardwired to False. Communication is<br />

possible via several <strong>com</strong>munication protocols<br />

including LonTalk, BACnet IP, and BACnet MS/TP.<br />

View Only<br />

Sup Fan Start Stop<br />

True when:<br />

Run Stop Input (hardwired) is AllowToRun and<br />

System enable is True and<br />

All fan alarms are False and<br />

Duct static pressure high limit is False (duct static<br />

VAV units) and<br />

Occupancy is True (occupied) or<br />

Night operation is True (night heating, cooling, or<br />

dehumidification)<br />

View Only<br />

Range: True, False<br />

Supply Fan Speed<br />

Displays the defined speed for the supply fan. The<br />

rooftop unit includes a variable frequency drive<br />

(VFD) for the supply fan motor. In constant volume<br />

operation, the speed of the fan remains constant at the<br />

defined speed (50-100%, adjustable). At 100%, the<br />

fan speed is determined according to the setup of the<br />

VFD (the design frequency, in Hz). The speed of the<br />

supply fan may be slowed for constant volume<br />

operation by adjusting the supply fan speed in the<br />

controller (50-110%). The minimum speed must not<br />

be less than 50% of the design flow to ensure proper<br />

heating and cooling operation.<br />

For variable air volume (VAV) applications, the<br />

speed of the fan is automatically determined by the<br />

controller (50-100%).<br />

Editable<br />

Range: 50-100%<br />

Default: 100%<br />

Sup Fan Status<br />

Reflects the status of the differential pressure switch<br />

for the supply fan (Universal Input 8). When the<br />

input contacts are closed, the supply fan status is<br />

True. When the input contacts are open, the supply<br />

fan status is False.<br />

View Only<br />

Range: True, False<br />

System Enable<br />

Must be True for normal unit operation. When<br />

system enable is False, the unit is <strong>com</strong>pletely<br />

disabled and will not operate.<br />

Editable<br />

Range: True, False<br />

Default: True<br />

<strong>Controls</strong> V2 <strong>IOM</strong> 18 May 2011<br />

Part Number 474626

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!