Heating<br />
Heating SP<br />
Displays the current heating setpoint that the unit will<br />
control the supply air temperature to when in heating<br />
mode.<br />
View Only<br />
Electric Heat<br />
Displays the signal in percent currently being sent to<br />
the electric heater (Analog Output, 5). The heating<br />
output percentage will increase, as the supply air<br />
temperature decreases.<br />
View Only<br />
Mod Heat Enable<br />
Displays the status of the modulating heat output<br />
(Digital Output, 6) of the controller.<br />
True when all <strong>com</strong>pressors are off and:<br />
Occupied heating operation or<br />
Unoccupied heating operation or<br />
Low supply air temperature<br />
View Only<br />
Mod Heat Pct<br />
Displays the signal in percent currently being sent to<br />
the modulating gas furnace (Analog Output, 3). The<br />
heating output percentage will increase, as the supply<br />
air temperature decreases.<br />
View Only<br />
HWVLV Action<br />
Used to change the operation of the modulating heat<br />
output that controls the hot water valve (if<br />
applicable). In Direct Action the output delivers<br />
0VDC at 0% and 10VDC at 100% heating capacity.<br />
In Reverse Action the output delivers 10VDC at 0%<br />
and 0VDC at 100% heating capacity.<br />
Editable<br />
Range: Direct Action, Reverse Action<br />
Default: Direct Action<br />
Mod Heat Stage 2<br />
Displays the status of the stage 2 modulating heat<br />
output (Digital Output, 7) of the controller.<br />
True when all <strong>com</strong>pressors are off and the heat<br />
enable <strong>com</strong>mand, modulating heat digital output has<br />
been on for two minutes and:<br />
Occupied heating operation or<br />
Unoccupied heating operation or<br />
Low supply air temperature<br />
View Only<br />
Mod Heat Stage 3<br />
Displays the status of the stage 3 modulating heat<br />
output (Digital Output, 3 of the expansion module) of<br />
the controller.<br />
True when all <strong>com</strong>pressors are off and the heat<br />
enable <strong>com</strong>mand, modulating heat stage 2 digital<br />
output has been on for two minutes and:<br />
Occupied heating operation or<br />
Unoccupied heating operation or<br />
Low supply air temperature<br />
View Only<br />
Winter Mode<br />
Allows user to select if the unit will go into a winter<br />
mode. Winter mode will allow the unit to slow the<br />
supply fan or modulate the outside air damper toward<br />
closed to keep the supply air setpoint once all heat<br />
sources are to 100% for more that 2 minutes.<br />
17. True (default)<br />
18. False<br />
Editable<br />
Winter Mode Act<br />
Allows the user to select what action the unit will<br />
take once it enters winter mode. Winter mode will<br />
slow the supply fan or modulate the outside air<br />
damper toward closed to keep the supply air setpoint<br />
once all heat sources are to 100% for more that 2<br />
minutes.<br />
19. Slow Fan (default)<br />
20. Mod Damper Closed<br />
Editable<br />
Amb Htg LockedOn<br />
Displays the status of the ambient heating lock on.<br />
The units heating source is locked on once the<br />
outside air temperature gets below the heating lockon<br />
setpoint.<br />
View Only<br />
Crnt Lockon Tmp<br />
Displays the outside air temperature that when below<br />
will lock the units first stage of heating on.<br />
View Only<br />
<strong>Controls</strong> V2 <strong>IOM</strong> 26 May 2011<br />
Part Number 474626