Heating<br />

Heating SP<br />

Displays the current heating setpoint that the unit will<br />

control the supply air temperature to when in heating<br />

mode.<br />

View Only<br />

Electric Heat<br />

Displays the signal in percent currently being sent to<br />

the electric heater (Analog Output, 5). The heating<br />

output percentage will increase, as the supply air<br />

temperature decreases.<br />

View Only<br />

Mod Heat Enable<br />

Displays the status of the modulating heat output<br />

(Digital Output, 6) of the controller.<br />

True when all <strong>com</strong>pressors are off and:<br />

Occupied heating operation or<br />

Unoccupied heating operation or<br />

Low supply air temperature<br />

View Only<br />

Mod Heat Pct<br />

Displays the signal in percent currently being sent to<br />

the modulating gas furnace (Analog Output, 3). The<br />

heating output percentage will increase, as the supply<br />

air temperature decreases.<br />

View Only<br />

HWVLV Action<br />

Used to change the operation of the modulating heat<br />

output that controls the hot water valve (if<br />

applicable). In Direct Action the output delivers<br />

0VDC at 0% and 10VDC at 100% heating capacity.<br />

In Reverse Action the output delivers 10VDC at 0%<br />

and 0VDC at 100% heating capacity.<br />

Editable<br />

Range: Direct Action, Reverse Action<br />

Default: Direct Action<br />

Mod Heat Stage 2<br />

Displays the status of the stage 2 modulating heat<br />

output (Digital Output, 7) of the controller.<br />

True when all <strong>com</strong>pressors are off and the heat<br />

enable <strong>com</strong>mand, modulating heat digital output has<br />

been on for two minutes and:<br />

Occupied heating operation or<br />

Unoccupied heating operation or<br />

Low supply air temperature<br />

View Only<br />

Mod Heat Stage 3<br />

Displays the status of the stage 3 modulating heat<br />

output (Digital Output, 3 of the expansion module) of<br />

the controller.<br />

True when all <strong>com</strong>pressors are off and the heat<br />

enable <strong>com</strong>mand, modulating heat stage 2 digital<br />

output has been on for two minutes and:<br />

Occupied heating operation or<br />

Unoccupied heating operation or<br />

Low supply air temperature<br />

View Only<br />

Winter Mode<br />

Allows user to select if the unit will go into a winter<br />

mode. Winter mode will allow the unit to slow the<br />

supply fan or modulate the outside air damper toward<br />

closed to keep the supply air setpoint once all heat<br />

sources are to 100% for more that 2 minutes.<br />

17. True (default)<br />

18. False<br />

Editable<br />

Winter Mode Act<br />

Allows the user to select what action the unit will<br />

take once it enters winter mode. Winter mode will<br />

slow the supply fan or modulate the outside air<br />

damper toward closed to keep the supply air setpoint<br />

once all heat sources are to 100% for more that 2<br />

minutes.<br />

19. Slow Fan (default)<br />

20. Mod Damper Closed<br />

Editable<br />

Amb Htg LockedOn<br />

Displays the status of the ambient heating lock on.<br />

The units heating source is locked on once the<br />

outside air temperature gets below the heating lockon<br />

setpoint.<br />

View Only<br />

Crnt Lockon Tmp<br />

Displays the outside air temperature that when below<br />

will lock the units first stage of heating on.<br />

View Only<br />

<strong>Controls</strong> V2 <strong>IOM</strong> 26 May 2011<br />