Cooling<br />
Cooling SP<br />
Displays the current cooling setpoint that the unit will<br />
control the supply air temperature to when in cooling<br />
mode.<br />
View Only<br />
Compressor 1 Command<br />
Represents the <strong>com</strong>manded state of Compressor 1,<br />
Digital Output 2 of the controller.<br />
View Only<br />
Compressor 2 Command<br />
Represents the <strong>com</strong>manded state of Compressor 2,<br />
Digital Output 3 of the controller.<br />
View Only<br />
Compressor 3 Command<br />
Represents the <strong>com</strong>manded state of Compressor 3,<br />
Digital Output 4 of the controller.<br />
View Only<br />
Compressor 4 Command<br />
Represents the <strong>com</strong>manded state of Compressor 4,<br />
Digital Output 5 of the controller.<br />
View Only<br />
H/L PC -A<br />
Represents the status of Universal Input 9. The high<br />
pressure cutout and low pressure cutout for circuit A,<br />
are wired in series. When tripped, the high pressure<br />
cutout requires manual reset, press the red button on<br />
the switch to reset. The low pressure cutout is<br />
automatically reset when the pressure is above the<br />
mechanical limit of the switch. The pressure cutout<br />
switches are located in the <strong>com</strong>pressor section of the<br />
unit.<br />
View Only<br />
Range: Normal, Alarm<br />
H/L PC -B<br />
Represents the status of Universal Input 10. The high<br />
pressure cutout and low pressure cutout for circuit B,<br />
are wired in series. When tripped, the high pressure<br />
cutout requires manual reset, press the red button on<br />
the switch to reset. The low pressure cutout is<br />
automatically reset when the pressure is above the<br />
mechanical limit of the switch. The pressure cutout<br />
switches are located in the <strong>com</strong>pressor section of the<br />
unit.<br />
View Only<br />
Range: Normal, Alarm<br />
Reheat Pct<br />
The capacity (in percentage) being delivered by the<br />
hot gas reheat valves and coil if installed. Hot gas<br />
reheat is controlled by dehumidification logic and in<br />
cooling mode to maintain the supply air temperature<br />
at setpoint.<br />
View Only<br />
Reheat Ena<br />
Displays the status of the hot gas reheat loop enable.<br />
True when <strong>com</strong>pressor 1 is enabled, not in shutdown,<br />
and unit is not in heating mode:<br />
Occupied dehumidification operation or<br />
Unoccupied dehumidification operation or<br />
Unit is cooling and supply temperature is below<br />
supply air setpoint.<br />
View Only<br />
Digital Pct<br />
The output in percentage of analog output 6<br />
controlling the loaded and unloaded percentage of the<br />
digital scroll <strong>com</strong>pressor.<br />
View Only<br />
Digital Scroll Priority<br />
This point allows the selection between temperature<br />
and humidity priority digital scroll operation during<br />
dehumidification.<br />
13. Temperature<br />
14. Humidity<br />
Editable<br />
Default: Temperature<br />
CWVLV Action<br />
Used to change the operation of the modulating<br />
cooling output that controls the chilled water valve (if<br />
applicable). In Direct Action the output delivers<br />
0VDC at 0% and 10VDC at 100% cooling capacity.<br />
In Reverse Action the output delivers 10VDC at 0%<br />
and 0VDC at 100% cooling capacity.<br />
Editable<br />
Range: Direct Action, Reverse Action<br />
Default: Direct Action<br />
Chilled Wtr Vlv Pct<br />
Represents signal controlling the chilled water valve<br />
on analog output 6.<br />
View Only<br />
CW Coil LL Stpt<br />
Displays and edits the coil temperature that when<br />
below will shut the unit down to protect the chilled<br />
water coil.<br />
Editable<br />
Range: -20-60°F<br />
Default: 36°F<br />
<strong>Controls</strong> V2 <strong>IOM</strong> 24 May 2011<br />
Part Number 474626