Heat Wheel<br />

Used to override the heat wheel percentage (speed).<br />

When output control is changed to Override, all<br />

outputs of the controller are driven Off (digital) and<br />

to 0% (analog). To manually override the control of<br />

the heat wheel, change the heat wheel to On. The<br />

heat wheel percentage (speed) may be adjusted as<br />

needed. The heat wheel automatically returns to Auto<br />

after 90 minutes or when output control is Auto.<br />

Editable<br />

Range: Off, On<br />

Default: Off<br />

Enable Heat Pump Water Valve<br />

Used to override the water valves on heat pump units.<br />

When output control is changed to Override, all<br />

outputs of the controller are driven Off (digital) and<br />

to 0% (analog). To manually override the control of<br />

the water valves, change the enable heat pump water<br />

valve to On. The water valve percentage (percent)<br />

may be adjusted as needed. The water valves<br />

automatically returns to Auto after 90 minutes or<br />

when output control is Auto.<br />

Editable<br />

Range: Off, On<br />

Default: Off<br />

Water Valve A Percentage<br />

Used to override the water valve A percentage<br />

(percent). When output control is changed to<br />

Override, all outputs of the controller are driven Off<br />

(digital) and to 0% (analog). To manually override<br />

the control of the water valves, change the enable<br />

heat pump water valve to On. The water valve A<br />

percentage (percent) may be adjusted as needed. The<br />

water valves automatically returns to Auto after 90<br />

minutes or when output control is Auto.<br />

Editable<br />

Range: 0-100%<br />

Default: 100%<br />

Water Valve B Percentage<br />

Used to override the water valve B percentage<br />

(percent). When output control is changed to<br />

Override, all outputs of the controller are driven Off<br />

(digital) and to 0% (analog). To manually override<br />

the control of the water valves, change the enable<br />

heat pump water valve to On. The water valve B<br />

percentage (percent) may be adjusted as needed. The<br />

water valves automatically returns to Auto after 90<br />

minutes or when output control is Auto.<br />

Editable<br />

Range: 0-100%<br />

Default: 100%<br />

Digital Scroll Percentage<br />

Used to override the digital scroll <strong>com</strong>pressor<br />

percentage (percent). When output control is changed<br />

to Override, all outputs of the controller are driven<br />

Off (digital) and to 0% (analog). To manually<br />

override the control of the digital scroll <strong>com</strong>pressor,<br />

change the enable digital scroll <strong>com</strong>pressor to On.<br />

The digital scroll <strong>com</strong>pressor percentage (percent)<br />

may be adjusted as needed. The water valves<br />

automatically returns to Auto after 90 minutes or<br />

when output control is Auto.<br />

Editable<br />

Range: 0-100%<br />

Default: 100%<br />

Chilled Wtr Vlv Ena<br />

Used to override the output for the chilled water<br />

valve. When output control is changed to Override,<br />

all outputs of the controller are driven Off (digital)<br />

and to 0% (analog). To manually override the control<br />

of chilled water valve output, change chilled water<br />

valve enable to On, then adjust the chilled water<br />

valve position to desired position. The <strong>com</strong>pressor 1<br />

output automatically returns to Auto after 60 minutes<br />

or when output control is Auto. Compressor<br />

overrides are only possible when the supply fan<br />

status is True and when all heat is off.<br />

Editable<br />

Range: Off, On<br />

Default: Off<br />

Chilled Vlv Pct<br />

Used to override the chilled water valve percentage<br />

(percent). When output control is changed to<br />

Override, all outputs of the controller are driven Off<br />

(digital) and to 0% (analog). To manually override<br />

the control of the chilled water valve, change the<br />

Chilled Wtr Vlv Ena to On. The water valve A<br />

percentage (percent) may be adjusted as needed. The<br />

water valves automatically returns to Auto after 90<br />

minutes or when output control is Auto.<br />

Editable<br />

Range: 0-100%<br />

Default: 100%<br />

<strong>Controls</strong> V2 <strong>IOM</strong> 30 May 2011<br />