Heat Wheel<br />
Used to override the heat wheel percentage (speed).<br />
When output control is changed to Override, all<br />
outputs of the controller are driven Off (digital) and<br />
to 0% (analog). To manually override the control of<br />
the heat wheel, change the heat wheel to On. The<br />
heat wheel percentage (speed) may be adjusted as<br />
needed. The heat wheel automatically returns to Auto<br />
after 90 minutes or when output control is Auto.<br />
Editable<br />
Range: Off, On<br />
Default: Off<br />
Enable Heat Pump Water Valve<br />
Used to override the water valves on heat pump units.<br />
When output control is changed to Override, all<br />
outputs of the controller are driven Off (digital) and<br />
to 0% (analog). To manually override the control of<br />
the water valves, change the enable heat pump water<br />
valve to On. The water valve percentage (percent)<br />
may be adjusted as needed. The water valves<br />
automatically returns to Auto after 90 minutes or<br />
when output control is Auto.<br />
Editable<br />
Range: Off, On<br />
Default: Off<br />
Water Valve A Percentage<br />
Used to override the water valve A percentage<br />
(percent). When output control is changed to<br />
Override, all outputs of the controller are driven Off<br />
(digital) and to 0% (analog). To manually override<br />
the control of the water valves, change the enable<br />
heat pump water valve to On. The water valve A<br />
percentage (percent) may be adjusted as needed. The<br />
water valves automatically returns to Auto after 90<br />
minutes or when output control is Auto.<br />
Editable<br />
Range: 0-100%<br />
Default: 100%<br />
Water Valve B Percentage<br />
Used to override the water valve B percentage<br />
(percent). When output control is changed to<br />
Override, all outputs of the controller are driven Off<br />
(digital) and to 0% (analog). To manually override<br />
the control of the water valves, change the enable<br />
heat pump water valve to On. The water valve B<br />
percentage (percent) may be adjusted as needed. The<br />
water valves automatically returns to Auto after 90<br />
minutes or when output control is Auto.<br />
Editable<br />
Range: 0-100%<br />
Default: 100%<br />
Digital Scroll Percentage<br />
Used to override the digital scroll <strong>com</strong>pressor<br />
percentage (percent). When output control is changed<br />
to Override, all outputs of the controller are driven<br />
Off (digital) and to 0% (analog). To manually<br />
override the control of the digital scroll <strong>com</strong>pressor,<br />
change the enable digital scroll <strong>com</strong>pressor to On.<br />
The digital scroll <strong>com</strong>pressor percentage (percent)<br />
may be adjusted as needed. The water valves<br />
automatically returns to Auto after 90 minutes or<br />
when output control is Auto.<br />
Editable<br />
Range: 0-100%<br />
Default: 100%<br />
Chilled Wtr Vlv Ena<br />
Used to override the output for the chilled water<br />
valve. When output control is changed to Override,<br />
all outputs of the controller are driven Off (digital)<br />
and to 0% (analog). To manually override the control<br />
of chilled water valve output, change chilled water<br />
valve enable to On, then adjust the chilled water<br />
valve position to desired position. The <strong>com</strong>pressor 1<br />
output automatically returns to Auto after 60 minutes<br />
or when output control is Auto. Compressor<br />
overrides are only possible when the supply fan<br />
status is True and when all heat is off.<br />
Editable<br />
Range: Off, On<br />
Default: Off<br />
Chilled Vlv Pct<br />
Used to override the chilled water valve percentage<br />
(percent). When output control is changed to<br />
Override, all outputs of the controller are driven Off<br />
(digital) and to 0% (analog). To manually override<br />
the control of the chilled water valve, change the<br />
Chilled Wtr Vlv Ena to On. The water valve A<br />
percentage (percent) may be adjusted as needed. The<br />
water valves automatically returns to Auto after 90<br />
minutes or when output control is Auto.<br />
Editable<br />
Range: 0-100%<br />
Default: 100%<br />
<strong>Controls</strong> V2 <strong>IOM</strong> 30 May 2011<br />
Part Number 474626