16 Point Module Optional Expansion Module<br />

1 Static Pressure Input Secondary<br />

2 Exhaust Temperature<br />

3 Pressure Sensor Circuit A<br />

4 Exhaust Fan Status<br />

5 CO2 Sensor<br />

6 Fan Speed / Damper Command<br />

7 Freezestat<br />

8 Pressure Sensor Circuit B<br />

Universal Inputs Terminals Notes<br />

U1<br />

0V<br />

0V<br />

U2<br />

U3<br />

0V<br />

0V<br />

U4<br />

U5<br />

0V<br />

0V<br />

U6<br />

U7<br />

0V<br />

0V<br />

U8<br />

0-10 VDC (display range varies)<br />

10kΩ Thermistor, Type III<br />

0-10 VDC (0-750 psi)<br />

Contact Closed = Fan ON<br />

0-10 VDC (0-2000 ppm)<br />

0-10 VDC (0-100%)<br />

Contact Closed = End Switch(es) Made, Freezestat<br />

NORMAL<br />

0-10 VDC (0-750 psi)<br />

<strong>Controls</strong> V2 <strong>IOM</strong> 6 May 2011<br />