Heat / Cool Changeover Setpoint<br />
The OAT that will determine if heating or cooling<br />
will have priority. When the OAT is above this<br />
temperature cooling will have priority, When the<br />
OAT is below this temperature heating will have<br />
priority. Set this value to Null and the controller will<br />
calculate this point automatically based on the current<br />
supply air temperature setpoint.<br />
Editable<br />
Range: 45-90°F<br />
Default: 65°F<br />
OAT Reset<br />
This point allows the use of the OAT reset. When<br />
enabled the supply air setpoint will be reset based on<br />
the outside air conditions When it is 40°F (Adj.) the<br />
reset will control to the supply only heating setpoint,<br />
as the OAT rises the supply setpoint will reset<br />
upwards towards the supply air cooling setpoint at<br />
80°F (Adj.).<br />
21. Enable Reset<br />
22. Disable Reset (Default)<br />
Editable<br />
Humidity Setpoints<br />
Occ Space RH Setpt<br />
Combined with the space relative humidity (RH)<br />
deadband to determine the (occupied and<br />
unoccupied) dehumidification mode. In the occupied<br />
mode, dehumidification is True when the outside<br />
dewpoint is greater than the outside dewpoint<br />
setpoint or the space relative humidity is greater than<br />
the space relative humidity setpoint.<br />
Dehumidification is False when the outside dewpoint<br />
is less than the outside dewpoint setpoint minus the<br />
outside dewpoint deadband and the space relative<br />
humidity is less than the space relative humidity<br />
setpoint minus the space relative humidity deadband.<br />
Notes: The outside dewpoint is calculated from the<br />
outside relative humidity and outside temperature.<br />
Unoccupied dehumidification can be determined<br />
based on space relative humidity or space dewpoint<br />
(selectable).<br />
Editable<br />
Range: 40-70%<br />
Default: 55%<br />
OA Dewpt Setpt<br />
Combined with the outside dewpoint deadband to<br />
determine the (occupied) dehumidification mode. In<br />
the occupied mode, dehumidification is True when<br />
the outside dewpoint is greater than the outside<br />
dewpoint setpoint or the space relative humidity is<br />
greater than the space relative humidity setpoint.<br />
Dehumidification is False when the outside dewpoint<br />
is less than the outside dewpoint setpoint minus the<br />
outside dewpoint deadband and the space relative<br />
humidity is less than the space relative humidity<br />
setpoint minus the space relative humidity deadband.<br />
Notes: The outside dewpoint is calculated from the<br />
outside relative humidity and outside temperature.<br />
Unoccupied dehumidification can be determined<br />
based on space relative humidity or space dewpoint<br />
(selectable) but does not use outside conditions.<br />
Editable<br />
Range: 40-100°F<br />
Default: 55°F<br />
<strong>Controls</strong> V2 <strong>IOM</strong> 32 May 2011<br />
Part Number 474626