Unit Shutdown Input<br />

Displays the status of the unit shutdown input<br />

(Universal Input 16) of the controller. When the input<br />

contacts are closed, the unit is allowed to run. When<br />

the input contacts are open, Shutdown is initiated<br />

(supply fan off, all heating and cooling off, outside<br />

air damper closed).<br />

View Only<br />

Range: Run, Stop<br />

Occupancy Input<br />

Represents the status of the hardwired occupancy<br />

input, Universal Input 15 on the controller. When the<br />

hardwired occupancy input is Closed, the input is<br />

Occupied. When the hardwired occupancy input is<br />

Open, the input is Unoccupied.<br />

View Only<br />

Low Limit Input<br />

Represents the status of Universal Input 7 on the<br />

expansion module, and is used for a hardwired low<br />

limit stat supplied with units ordered with hot water<br />

heat.<br />

View Only<br />

Range: Normal, Alarm<br />

Head Press AO<br />

Displays the signal in percent Speed being delivered<br />

to the head pressure control VFD, to maintain the<br />

condensing temperature in cooling mode and suction<br />

temperature in heating mode.<br />

View Only<br />

Head Press DO<br />

Displays the status of the head pressure control<br />

digital output, to maintain the condensing<br />

temperature in cooling mode and suction temperature<br />

in heating mode.<br />

View Only<br />

Reversing Valve<br />

Displays the status of the reversing valve digital<br />

output, the digital output will be off when in cooling<br />

mode and on in heating mode.<br />

View Only<br />

Software Version<br />

Displays the version of the application software in<br />

the controller and should not be edited.<br />

Editable<br />

Default: r31<br />

Defrost Mode<br />

Reflects the status of the air source heat pumps<br />

defrost mode Defrost mode will be initiated when the<br />

suction pressure drops below the outside air dewpoint<br />

minus an offset for a reset period of time. When in<br />

defrost mode the all controlled condenser fans will<br />

turn off and the unit will run in cooling mode to heat<br />

up and melt the frost built up on the outdoor coil.<br />

View Only<br />

Range: True, False<br />

<strong>Controls</strong> V2 <strong>IOM</strong> 20 May 2011<br />