Unit Shutdown Input<br />
Displays the status of the unit shutdown input<br />
(Universal Input 16) of the controller. When the input<br />
contacts are closed, the unit is allowed to run. When<br />
the input contacts are open, Shutdown is initiated<br />
(supply fan off, all heating and cooling off, outside<br />
air damper closed).<br />
View Only<br />
Range: Run, Stop<br />
Occupancy Input<br />
Represents the status of the hardwired occupancy<br />
input, Universal Input 15 on the controller. When the<br />
hardwired occupancy input is Closed, the input is<br />
Occupied. When the hardwired occupancy input is<br />
Open, the input is Unoccupied.<br />
View Only<br />
Low Limit Input<br />
Represents the status of Universal Input 7 on the<br />
expansion module, and is used for a hardwired low<br />
limit stat supplied with units ordered with hot water<br />
heat.<br />
View Only<br />
Range: Normal, Alarm<br />
Head Press AO<br />
Displays the signal in percent Speed being delivered<br />
to the head pressure control VFD, to maintain the<br />
condensing temperature in cooling mode and suction<br />
temperature in heating mode.<br />
View Only<br />
Head Press DO<br />
Displays the status of the head pressure control<br />
digital output, to maintain the condensing<br />
temperature in cooling mode and suction temperature<br />
in heating mode.<br />
View Only<br />
Reversing Valve<br />
Displays the status of the reversing valve digital<br />
output, the digital output will be off when in cooling<br />
mode and on in heating mode.<br />
View Only<br />
Software Version<br />
Displays the version of the application software in<br />
the controller and should not be edited.<br />
Editable<br />
Default: r31<br />
Defrost Mode<br />
Reflects the status of the air source heat pumps<br />
defrost mode Defrost mode will be initiated when the<br />
suction pressure drops below the outside air dewpoint<br />
minus an offset for a reset period of time. When in<br />
defrost mode the all controlled condenser fans will<br />
turn off and the unit will run in cooling mode to heat<br />
up and melt the frost built up on the outdoor coil.<br />
View Only<br />
Range: True, False<br />