Unocc RH Setpt<br />
In the unoccupied mode, Unoccupied Cooling +<br />
Dehumidification is True when the space humidity is<br />
greater than the space unoccupied humidity setpoint,<br />
and the unoccupied dehumidification control is set to<br />
space humidity. Unoccupied Cooling +<br />
Dehumidification is False when the space humidity is<br />
less than the unoccupied space humidity setpoint<br />
minus one half the space unoccupied humidity<br />
deadband. Unoccupied dehumidification can be<br />
determined based on space relative humidity or space<br />
dewpoint (selectable) but does not use outside<br />
conditions.<br />
Editable<br />
Range: 0-100%<br />
Default: 55°F<br />
Occ Hardwired<br />
Must be False if the occupancy is determined either<br />
by the local time clock/schedule or a network<br />
<strong>com</strong>mand (LonTalk, BACnet, etc.). Occupancy<br />
Hardwired must be True if the occupancy is to be<br />
determined by the hardwired occupancy input -<br />
Universal Input 15 on the controller.<br />
Editable<br />
Range: False, True<br />
Default: False<br />
Unocc Clg Sup SP<br />
If the night cool style is set to setpoint, the unit will<br />
control to this setpoint any time it is running in<br />
unoccupied cooling mode.<br />
Editable<br />
Range: 55°F<br />
Default: 45 to 95°F<br />
Unocc Ht Sup SP<br />
If the night heat style is set to setpoint, the unit will<br />
control to this setpoint any time it is running in<br />
unoccupied heating mode.<br />
Editable<br />
Range: 90°F<br />
Default: 45 to 95°F<br />
Unocc Fan Spd<br />
Displays and edits the speed the supply fan VFD will<br />
run when unoccupied. When unit is started in night<br />
heating, cooling, or dehumidification the supply fan<br />
will run at this percentage of full speed. Unless the<br />
supply fan is controlling to maintain a duct or space<br />
static pressure, CO2, or is set up for a remote fan<br />
input.<br />
Editable<br />
Range: 50-100%<br />
Default: 100%<br />
Range: True, False<br />
UnOcc Dmp Pos<br />
Position of the damper on recirculation units during<br />
unoccupied operation.<br />
Editable<br />
Range: 0-100%<br />
Default: 0%<br />
Night Cool Style<br />
Allows user to select how the unit maintains the<br />
unoccupied cooling setpoint. Reset will reset the<br />
supply air based on space temperature. Setpoint will<br />
allow the units supply air temperature setpoint to be<br />
set, and the unit will supply this temperature air any<br />
time the unit is in unoccupied cooling mode.<br />
26. Reset (default)<br />
27. Setpoint<br />
Editable<br />
Night Heat Style<br />
Allows user to select how the unit maintains the<br />
unoccupied heating setpoint. Reset will reset the<br />
supply air based on space temperature. Setpoint will<br />
allow the units supply air temperature setpoint to be<br />
set, and the unit will supply this temperature air any<br />
time the unit is in unoccupied heating mode.<br />
28. Reset (default)<br />
29. Setpoint<br />
Editable<br />
Standby Heat SP<br />
Displays and sets the supply air temperature the unit<br />
will produce when in standby mode, heating, and set<br />
to supply air only.<br />
Default: 65°F<br />
Range: 45 to 90°F<br />
Standby Cool SP<br />
Displays and sets the supply air temperature the unit<br />
will produce when in standby mode, cooling, and set<br />
to supply air only.<br />
Default: 75°F<br />
Range: 50 to 110°F<br />
Stndby Spc Offst<br />
Displays and sets the offset from the occupied space<br />
temperature setpoint, when the unit is in standby<br />
mode and resetting the supply temperature based on<br />
the space temperature. The offset is divided in half<br />
and then added to the cooling setpoint, and subtracted<br />
from the heating setpoint. For example if the unit is<br />
set to a 70°F space setpoint and the unit is put in<br />
standby mode with the occupied standby space offset<br />
left at the default of 4°F, the heating setpoint would<br />
be 68°F, and cooling setpoint would be 72°F.<br />
Default: 4°F<br />
Range: 0 to 20°F<br />