02.01.2015 Views

Valent_IOM_Controls - RJI-Sales.com

Valent_IOM_Controls - RJI-Sales.com

Valent_IOM_Controls - RJI-Sales.com

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Air Flow Measuring Station (Universal Input 11)<br />

Measured by the either the Inlet cone sensor or AMD<br />

damper located in the outside air inlet. This is the<br />

actual air flow being measured in CFM as calculated<br />

by the factory calibrated air flow measuring station.<br />

View Only<br />

Primary Static Pressure Input (Universal Input 12)<br />

Displays the interpreted value of the voltage read<br />

from the space or duct static pressure sensor. The<br />

static pressure sensor should be field installed in the<br />

space/duct served by the rooftop unit. The output<br />

signal from the sensor must be 0-10 VDC. The space<br />

/ duct static pressure sensor, when used, must be<br />

connected to Universal Input 12 on the 34 point<br />

module depending on the configuration of the<br />

ventilator. For the sensor voltage to be interpreted<br />

correctly, the conversion scale and offset values must<br />

be set up correctly for that device (refer to the<br />

Appendix).<br />

Filter Status Input (Universal Input 13)<br />

The filter status differential pressure switch<br />

(optional) indicates the pressure across the filters. If<br />

the contacts close for five continuous minutes on the<br />

pressure switch, the controller interprets a dirty filter<br />

condition. The unit operates normally, but the alarm<br />

LED is illuminated on the controller.<br />

Space Setpoint Adjustment (Universal Input 14)<br />

Represents the amount of offset currently being<br />

applied to the space temperature setpoint. A positive<br />

value will increase the space temperature setpoint by<br />

the amount shown. A negative value will decrease the<br />

space temperature setpoint by the amount shown.<br />

Occupancy Input (Universal Input 15)<br />

The hardwired occupancy input of the controller can<br />

be used to determine the occupancy mode. When the<br />

input contacts are closed, the mode of the controller<br />

is occupied. When the contacts are open, the mode is<br />

unoccupied. The factory-installed jumper wire should<br />

be removed when a field-installed occupancy device<br />

is used. If the hardwired input is used to determine<br />

the occupancy of the controller, the OCC<br />

HARDWIRED field (operator interface or PC tool)<br />

should be set to TRUE. When the hardwired input is<br />

not being used to determine the occupancy, the OCC<br />

HARDWIRED field should be set to False<br />

Shutdown Input (Universal Input 16)<br />

The shutdown input of the controller prevents unit<br />

operation when the input contacts are open. The<br />

factory-installed jumper wire should be removed<br />

when a field-installed shutdown device is used.<br />

16 Point Module<br />

Secondary Static Pressure Input (Universal Input 1)<br />

When the unit is equipped with both a space and duct<br />

static pressure sensor, universal input 1 of the 16<br />

point module will always be used for the duct static<br />

pressure sensor input. For the sensor voltage to be<br />

interpreted correctly, the conversion scale and offset<br />

values must be set up correctly for that device (refer<br />

to the Appendix).<br />

Exhaust Temperature (Universal Input 2)<br />

Measured with a thermistor (type III) factory<br />

installed at the exhaust side of the heat wheel. The<br />

sensor is wired to Universal Input 2 on the expansion<br />

module of the controller.<br />

Pressure Sensor Circuit A (Universal Input 3)<br />

Measured with a pressure transducer factory installed<br />

in the refrigeration piping. The signal from the sensor<br />

will be a 0-10 VDC signal with a range of 0-750 psi.<br />

The sensor is wired to Universal Input 3 on the<br />

expansion module of the controller.<br />

Exhaust Fan Status (Universal Input 4)<br />

Reflects the status of the differential pressure switch<br />

for the exhaust fan (Universal Input 4, expansion 16<br />

point module). When the input contacts are closed,<br />

the exhaust fan status is true. When the input contacts<br />

are open, the exhaust fan status is false.<br />

CO2 Sensor (Universal Input 5)<br />

Measured by the field installed CO2 sensor located in<br />

the space/room served by the rooftop unit. That<br />

sensor provides a 0-10 VDC signal to the controller,<br />

Universal Input 5, of the expansion module that<br />

corresponds to the space CO2: 0 VDC = 500 ppm<br />

CO2, 10 VDC = 1500 ppm CO2.<br />

Fan / Damper Remote Command (Universal Input 6)<br />

Displays the fan speed <strong>com</strong>mand <strong>com</strong>ing from the<br />

remote fan input, universal input 6 on the expansion<br />

16 point module. 0vdc will equal the units minimum<br />

supply fan speed, and 10 vdc equals the units<br />

maximum supply fan speed.<br />

Low Limit (Universal Input 7)<br />

Displays the status of the low limit sensor, when<br />

applicable (factory supplied with hot water coils).<br />

The ventilator will go into a low limit alarm, shutting<br />

down the fans, closing the outside air damper, and<br />

forcing the hot water valve open, any time the input<br />

is closed. Once triggered the low limit will be<br />

enabled for five minutes and then automatically reset.<br />

After three strikes the controller must be reset. Input<br />

open=normal, input closed=alarm.<br />

<strong>Controls</strong> V2 <strong>IOM</strong> 8 May 2011<br />

Part Number 474626

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!