Duct Static Press<br />

Displays the interpreted value of the voltage read<br />

from the duct static pressure sensor. The duct static<br />

pressure sensor should be field installed<br />

approximately 2/3 down the supply duct. The output<br />

signal from the sensor must be 0-10 VDC. The duct<br />

static pressure sensor, when used, must be connected<br />

to Universal Input 12 on the 34 point module or<br />

Universal Input 1 on the 16 point module on the<br />

controller depending on the configuration of the<br />

ventilator. For the sensor voltage to be interpreted<br />

correctly, the conversion scale and offset values must<br />

be set up correctly for that device (refer to the<br />

Appendix).<br />

View Only<br />

Space Enthalpy<br />

Calculated based on the field installed (factory<br />

provided if ordered) space temperature sensor and<br />

field installed (factory provided if ordered) space<br />

humidity sensor.<br />

View Only<br />

Outside Air Enthalpy<br />

Calculated based on factory installed RH sensor and<br />

factory installed outside air temperature sensor.<br />

View Only<br />

AFMS Sensor<br />

Measured by the either the Inlet cone sensor or AMD<br />

damper located in the outside air inlet. This is the<br />

actual air flow being measured in CFM as calculated<br />

by the factory calibrated air flow measuring station.<br />

View Only<br />

HP Ckt A Press<br />

Measured with a pressure transducer factory installed<br />

in the refrigeration piping. The signal from the sensor<br />

will be a 0-10 VDC signal with a range of 0-750 psi.<br />

The sensor is wired to Universal Input 3 on the<br />

expansion module of the controller.<br />

View Only<br />

HP Ckt B Press<br />

Measured with a pressure transducer factory installed<br />

in the refrigeration piping. The signal from the sensor<br />

will be a 0-10 VDC signal with a range of 0-750 psi.<br />

The sensor is wired to Universal Input 8 on the<br />

expansion module of the controller.<br />

View Only<br />

HP Ckt A Temp<br />

Displays the calculated value for circuit A's<br />

condensing temperature when in cooling mode, and<br />

suction temperature when in heating mode.<br />

View Only<br />

HP Ckt B Temp<br />

Displays the calculated value for circuit B's<br />

condensing temperature when in cooling mode, and<br />

suction temperature when in heating mode.<br />

View Only<br />

<strong>Controls</strong> V2 <strong>IOM</strong> 22 May 2011<br />

Part Number 474626