Duct Static Press<br />
Displays the interpreted value of the voltage read<br />
from the duct static pressure sensor. The duct static<br />
pressure sensor should be field installed<br />
approximately 2/3 down the supply duct. The output<br />
signal from the sensor must be 0-10 VDC. The duct<br />
static pressure sensor, when used, must be connected<br />
to Universal Input 12 on the 34 point module or<br />
Universal Input 1 on the 16 point module on the<br />
controller depending on the configuration of the<br />
ventilator. For the sensor voltage to be interpreted<br />
correctly, the conversion scale and offset values must<br />
be set up correctly for that device (refer to the<br />
Appendix).<br />
View Only<br />
Space Enthalpy<br />
Calculated based on the field installed (factory<br />
provided if ordered) space temperature sensor and<br />
field installed (factory provided if ordered) space<br />
humidity sensor.<br />
View Only<br />
Outside Air Enthalpy<br />
Calculated based on factory installed RH sensor and<br />
factory installed outside air temperature sensor.<br />
View Only<br />
AFMS Sensor<br />
Measured by the either the Inlet cone sensor or AMD<br />
damper located in the outside air inlet. This is the<br />
actual air flow being measured in CFM as calculated<br />
by the factory calibrated air flow measuring station.<br />
View Only<br />
HP Ckt A Press<br />
Measured with a pressure transducer factory installed<br />
in the refrigeration piping. The signal from the sensor<br />
will be a 0-10 VDC signal with a range of 0-750 psi.<br />
The sensor is wired to Universal Input 3 on the<br />
expansion module of the controller.<br />
View Only<br />
HP Ckt B Press<br />
Measured with a pressure transducer factory installed<br />
in the refrigeration piping. The signal from the sensor<br />
will be a 0-10 VDC signal with a range of 0-750 psi.<br />
The sensor is wired to Universal Input 8 on the<br />
expansion module of the controller.<br />
View Only<br />
HP Ckt A Temp<br />
Displays the calculated value for circuit A's<br />
condensing temperature when in cooling mode, and<br />
suction temperature when in heating mode.<br />
View Only<br />
HP Ckt B Temp<br />
Displays the calculated value for circuit B's<br />
condensing temperature when in cooling mode, and<br />
suction temperature when in heating mode.<br />
View Only<br />
<strong>Controls</strong> V2 <strong>IOM</strong> 22 May 2011<br />
Part Number 474626