Compressor 4<br />

Used to override the output for <strong>com</strong>pressor 4. When<br />

output control is changed to Override, all outputs of<br />

the controller are driven Off (digital) and to 0%<br />

(analog). To manually override the control of the<br />

<strong>com</strong>pressor 4 output, change <strong>com</strong>pressor 4 to On.<br />

The <strong>com</strong>pressor 4 output automatically returns to<br />

Auto after 60 minutes or when output control is Auto.<br />

Compressor overrides are only possible when the<br />

supply fan status is True and when all heat is off.<br />

Editable<br />

Range: Off, On<br />

Default: Off<br />

Digital Scroll Percentage<br />

Used to override the digital scroll <strong>com</strong>pressor<br />

percentage (percent). When output control is changed<br />

to Override, all outputs of the controller are driven<br />

Off (digital) and to 0% (analog). To manually<br />

override the control of the digital scroll <strong>com</strong>pressor,<br />

change the enable digital scroll <strong>com</strong>pressor to On.<br />

The digital scroll <strong>com</strong>pressor percentage (percent)<br />

may be adjusted as needed. The water valves<br />

automatically returns to Auto after 90 minutes or<br />

when output control is Auto.<br />

Editable<br />

Range: 0-100%<br />

Default: 100%<br />

Hot Gas Reheat<br />

Used to override the output for hot gas reheat. When<br />

output control is changed to Override, all outputs of<br />

the controller are driven Off (digital) and to 0%<br />

(analog). To manually override the control of the hot<br />

gas reheat, change hot gas reheat to On and edit the<br />

hot gas reheat percentage as needed. The hot gas<br />

reheat output automatically returns to Auto after 30<br />

minutes or when output control is Auto. Hot gas<br />

reheat overrides are only possible when the<br />

<strong>com</strong>pressor 1 is on.<br />

Editable<br />

Range: Off, On<br />

Default: Off<br />

Hot Gas Reheat Pct<br />

Used to override the percentage of the hot gas reheat.<br />

When output control is changed to Override, all<br />

outputs of the controller are driven Off (digital) and<br />

to 0% (analog). To manually override the control of<br />

the hot gas reheat, change hot gas reheat to On and<br />

edit the hot gas reheat percentage as needed. The hot<br />

gas reheat output automatically returns to Auto after<br />

30 minutes or when output control is Auto. Hot gas<br />

reheat overrides are only possible when the<br />

<strong>com</strong>pressor 1 is on.<br />

Editable<br />

Range: 0-100%<br />

Default: 100%<br />

Electric Heat<br />

Used to override the output for electric heat. When<br />

output control is changed to Override, all outputs of<br />

the controller are driven Off (digital) and to 0%<br />

(analog). To manually override the control of the<br />

electric heat, change electric heat to On and edit the<br />

electric heat percentage as needed. The electric heat<br />

output automatically returns to Auto after 30 minutes<br />

or when output control is Auto. Electric heat<br />

overrides are only possible when the supply fan<br />

status is True and all <strong>com</strong>pressors are off.<br />

Editable<br />

Range: Off, On<br />

Default: Off<br />

Elec Ht Pct<br />

Used to override the percentage of the electric heat.<br />

When output control is changed to Override, all<br />

outputs of the controller are driven Off (digital) and<br />

to 0% (analog). To manually override the control of<br />

the electric heat, change electric heat to On and edit<br />

the electric heat percentage as needed. The electric<br />

heat output automatically returns to Auto after 30<br />

minutes or when output control is Auto. Electric heat<br />

overrides are only possible when the supply fan<br />

status is True and all <strong>com</strong>pressors are off.<br />

Editable<br />

Range: 0-100%<br />

Default: 100%<br />

<strong>Controls</strong> V2 <strong>IOM</strong> 28 May 2011<br />