Unocc DB<br />
(5°F, adjustable) is <strong>com</strong>bined with the space<br />
unoccupied heating and cooling setpoints (60°F and<br />
80°F, adjustable) to determine unoccupied operation.<br />
Editable<br />
Range: 0-10°F<br />
Default: 5°F<br />
Unocc Spc Dwpt DB<br />
When the space dewpoint is greater than the<br />
unoccupied space dewpoint setpoint plus one half the<br />
space unoccupied dewpoint deadband, the unit will<br />
enter Unoccupied Cooling + Dehumidification mode.<br />
Editable<br />
Range: 0-10°F<br />
Default: 6°F<br />
Unocc RH DB<br />
When the space humidity is greater than the<br />
unoccupied space humidity setpoint plus one half the<br />
space unoccupied humidity deadband, the unit will<br />
enter Unoccupied Cooling + Dehumidification mode.<br />
Editable<br />
Range: 0-10%<br />
Default: 5%<br />
Amb Clg Lockin<br />
When the outside air temperature is greater than the<br />
outside temp to lock on <strong>com</strong>pressor 1 setpoint,<br />
<strong>com</strong>pressor 1 remains on and does not cycle. The<br />
logic is only active during the occupied mode.<br />
Editable<br />
Range: 60-100°F<br />
Default: 75°F<br />
Unocc Clg Bst<br />
Offsets the unoccupied cooling setpoint by this value<br />
to cool down the space and shut down faster saving<br />
energy.<br />
Editable<br />
Range: 0-15°F<br />
Default: 10°F<br />
Unocc Htg Bst<br />
Offsets the unoccupied heating setpoint by this value<br />
to heat the space up and shut down faster saving<br />
energy.<br />
Editable<br />
Range: 0-15°F<br />
Default: 10°F<br />
Cmp 1 Amb L'out<br />
Displays and edits the <strong>com</strong>pressor ambient lockout<br />
setpoint. Compressor 1 operation is disabled when<br />
the outside air temperature is 2°F less than this<br />
ambient lockout setpoint (55°F, adjustable).<br />
Compressor 1 operation is enabled when the outside<br />
air temperature is greater than this ambient lockout<br />
setpoint.<br />
Editable<br />
Range: 45-90°F<br />
Default: 55°F<br />
Cmp 2 Amb L'out<br />
Displays and edits the <strong>com</strong>pressor ambient lockout<br />
setpoint. Compressor 2 operation is disabled when<br />
the outside air temperature is less than this ambient<br />
lockout setpoint (58°F, adjustable). Compressor 2<br />
operation is enabled when the outside air temperature<br />
is 3°F greater than this ambient lockout setpoint.<br />
Editable<br />
Range: 50-90°F<br />
Default: 60°F<br />
Cmp 3& 4 Amb L'out<br />
Displays and edits the <strong>com</strong>pressor ambient lockout<br />
setpoint. Compressors 3 and 4 are disabled when the<br />
outside air temperature is less than this ambient<br />
lockout setpoint (61°F, adjustable). Compressors 3<br />
and 4 are enabled when the outside air temperature is<br />
3°F greater than this ambient lockout setpoint.<br />
Editable<br />
Range: 50-90°F<br />
Default: 60°F<br />
Warm Up Ena<br />
Allows user to select if the unit is allowed to go into<br />
a warm up mode. Warm up mode will allow the unit<br />
too, once a day on startup. If the space temperature is<br />
lower than the space setpoint the unit will hold the<br />
outside air dampers closed until the unit warms the<br />
space up to setpoint.<br />
39. Disabled (default)<br />
40. Enabled<br />
Editable<br />
Cool Down Ena<br />
Allows user to select if the unit is allowed to go into<br />
a cool down mode. Cool down mode will allow the<br />
unit too, once a day on startup. If the space<br />
temperature is higher than the space setpoint the unit<br />
will hold the outside air dampers closed until the unit<br />
cools the space down to setpoint.<br />
41. Cool Down Disabled (default)<br />
42. Cool Down Enabled<br />
Editable<br />
<strong>Controls</strong> V2 <strong>IOM</strong> 40 May 2011<br />
Part Number 474626