Unocc DB<br />

(5°F, adjustable) is <strong>com</strong>bined with the space<br />

unoccupied heating and cooling setpoints (60°F and<br />

80°F, adjustable) to determine unoccupied operation.<br />

Editable<br />

Range: 0-10°F<br />

Default: 5°F<br />

Unocc Spc Dwpt DB<br />

When the space dewpoint is greater than the<br />

unoccupied space dewpoint setpoint plus one half the<br />

space unoccupied dewpoint deadband, the unit will<br />

enter Unoccupied Cooling + Dehumidification mode.<br />

Editable<br />

Range: 0-10°F<br />

Default: 6°F<br />

Unocc RH DB<br />

When the space humidity is greater than the<br />

unoccupied space humidity setpoint plus one half the<br />

space unoccupied humidity deadband, the unit will<br />

enter Unoccupied Cooling + Dehumidification mode.<br />

Editable<br />

Range: 0-10%<br />

Default: 5%<br />

Amb Clg Lockin<br />

When the outside air temperature is greater than the<br />

outside temp to lock on <strong>com</strong>pressor 1 setpoint,<br />

<strong>com</strong>pressor 1 remains on and does not cycle. The<br />

logic is only active during the occupied mode.<br />

Editable<br />

Range: 60-100°F<br />

Default: 75°F<br />

Unocc Clg Bst<br />

Offsets the unoccupied cooling setpoint by this value<br />

to cool down the space and shut down faster saving<br />

energy.<br />

Editable<br />

Range: 0-15°F<br />

Default: 10°F<br />

Unocc Htg Bst<br />

Offsets the unoccupied heating setpoint by this value<br />

to heat the space up and shut down faster saving<br />

energy.<br />

Editable<br />

Range: 0-15°F<br />

Default: 10°F<br />

Cmp 1 Amb L'out<br />

Displays and edits the <strong>com</strong>pressor ambient lockout<br />

setpoint. Compressor 1 operation is disabled when<br />

the outside air temperature is 2°F less than this<br />

ambient lockout setpoint (55°F, adjustable).<br />

Compressor 1 operation is enabled when the outside<br />

air temperature is greater than this ambient lockout<br />

setpoint.<br />

Editable<br />

Range: 45-90°F<br />

Default: 55°F<br />

Cmp 2 Amb L'out<br />

Displays and edits the <strong>com</strong>pressor ambient lockout<br />

setpoint. Compressor 2 operation is disabled when<br />

the outside air temperature is less than this ambient<br />

lockout setpoint (58°F, adjustable). Compressor 2<br />

operation is enabled when the outside air temperature<br />

is 3°F greater than this ambient lockout setpoint.<br />

Editable<br />

Range: 50-90°F<br />

Default: 60°F<br />

Cmp 3& 4 Amb L'out<br />

Displays and edits the <strong>com</strong>pressor ambient lockout<br />

setpoint. Compressors 3 and 4 are disabled when the<br />

outside air temperature is less than this ambient<br />

lockout setpoint (61°F, adjustable). Compressors 3<br />

and 4 are enabled when the outside air temperature is<br />

3°F greater than this ambient lockout setpoint.<br />

Editable<br />

Range: 50-90°F<br />

Default: 60°F<br />

Warm Up Ena<br />

Allows user to select if the unit is allowed to go into<br />

a warm up mode. Warm up mode will allow the unit<br />

too, once a day on startup. If the space temperature is<br />

lower than the space setpoint the unit will hold the<br />

outside air dampers closed until the unit warms the<br />

space up to setpoint.<br />

39. Disabled (default)<br />

40. Enabled<br />

Editable<br />

Cool Down Ena<br />

Allows user to select if the unit is allowed to go into<br />

a cool down mode. Cool down mode will allow the<br />

unit too, once a day on startup. If the space<br />

temperature is higher than the space setpoint the unit<br />

will hold the outside air dampers closed until the unit<br />

cools the space down to setpoint.<br />

41. Cool Down Disabled (default)<br />

42. Cool Down Enabled<br />

Editable<br />

<strong>Controls</strong> V2 <strong>IOM</strong> 40 May 2011<br />

Part Number 474626