Max Master<br />

Set Max Master to the largest known master device<br />

MSTP Address on the network, with possible room<br />

for expansion if needed.<br />

Editable<br />

Range: 0-127<br />

Default: 127<br />

Max Info Frames<br />

Max Info Frames property controls how many<br />

messages are sent before passing the token, and may<br />

be increased up to 50 to increase performance in<br />

some cases.<br />

Editable<br />

Range: 5-50<br />

Default: 20<br />

Lonworks<br />

Neuron<br />

The Neuron ID is a hardware address that will change<br />

if the hardware changes. Each LonWorks device has<br />

a unique 48 bit Neuron ID that was burnt into the<br />

Neuron chip when it was manufactured, resulting in<br />

approximately 300 trillion different <strong>com</strong>binations.<br />

The Neuron ID is broadcast through the network<br />

when a device is pinned so that a logical address<br />

(Subnet/Node ID) can be assigned. The network<br />

management tool must have the Neuron ID to<br />

<strong>com</strong>mission a device. The Neuron ID does not<br />

contain information about the address of a device. A<br />

device’s Neuron ID and Subnet/Node ID can be<br />

found in the Identifiers tab of the device’s properties.<br />

See also Subnet/Node ID.<br />

View Only<br />

Service Pin<br />

The service pin generates a service-pin message that<br />

contains the Neuron ID and the program code<br />

identification of the node. A service-pin message is a<br />

network message that is generated by a node<br />

and broadcast on the network. It can be used to<br />

<strong>com</strong>mission the LONWORKS network. Set to True<br />

to generate a service pin and the value will<br />

automatically be reset back to False.<br />

55. False (default)<br />

56. True<br />

Editable<br />

<strong>Controls</strong> V2 <strong>IOM</strong> 44 May 2011<br />

Part Number 474626