Command Set<br />

Command Syntex<br />

Command<br />

Response<br />

Syntex<br />

$AAM(cr) !AA(name)(cr)name<br />

: 4017P<br />

$AA7CiRrr(cr)C :<br />

channeli : 0 ~ 7R :<br />

Rangerr : Range<br />

code<br />

$AA8Ci(cr)i= 0 ~ 7<br />

(channel number)<br />

$AAXnnnn(cr)nnnn:<br />

0000 ~ 9999unit:<br />

0.1sec<br />

$AAY(cr) !AAnnnn(cr)nnnn:<br />

0000 ~<br />

9999<br />

$AAB(cr) !AANN(cr)NN:<br />

00 ~ FFbit<br />

value : 0 for<br />

normal, 1 for<br />

open wire<br />

$AA3(cr) >snnnn.n(cr)s:<br />

+ or -n: digit<br />

$AA9SNNNN(cr)<br />

S: + or -NNNN: 0000<br />

~ FFFF<br />

4-22 <strong>ADAM</strong> <strong>4000</strong> <strong>Series</strong> User's Manual<br />

Command Description<br />

The command request the<br />

module at address AA to<br />

return the module name<br />

!AA(cr) R : Range<br />

rr : +/-0~20mA: 0x06<br />

+/-4~20mA: 0x07<br />

J type : 0x0e<br />

K type : 0x0f<br />

T type : 0x10<br />

E type : 0x11<br />

R type : 0x12<br />

S type : 0x13<br />

B type : 0x14<br />

!AACiRrr(cr) Get the input type of the<br />

assignment channel<br />

!AA(cr) Set communication WDT value<br />

form 0000 ~ 9999 (if value is<br />

0000 the communication WDT<br />

function will be disable)<br />

Get communication WDT<br />

setting value<br />

Get the channel operating<br />

statusWhen bit value is 0, it<br />

mean this channel is in normal<br />

operating, when bit value is 1,<br />

it mean this channel is<br />

opening wire<br />

Command<br />

Example<br />

Command<br />

response<br />

Example<br />

$03M(cr) !034018P(cr)<br />

$057R0EW-<br />

5C6(cr)<br />

!05(cr)<br />

$058C6(cr) !05C6R08(cr)<br />

$05X0030(cr)<br />

!05(cr)<br />

$05Y(cr) !050030(cr)<br />

$12B(cr) !1205(cr)05<br />

mean channel<br />

0 and 2 is<br />

open<br />

Get the CJC current value $063(cr) >+0035.8(cr)<br />

!AA(cr) Calibrates an analog input<br />

module to adjust for offset<br />

errors of its CJC sensors<br />

$079+0500-<br />

(cr)<br />

!07(cr)