Technical specifications<br />

A.1 <strong>ADAM</strong>-4011 Thermocouple Input Module<br />

Table A-1 <strong>ADAM</strong>-4011 Specifications<br />

Input range J, K, T, E, R, S and B Thermocouple<br />

±15 mV, ±50 mV, ±100 mV, ±500mV,<br />

±1 V, ±2.5 V, and ±20mA<br />

Output RS-485 (2-Wire)<br />

speed (in bps) 1200, 2400, 4800, 9600, 19.2K, 38.4K<br />

maximum distance <strong>4000</strong> ft. (1200 m.)<br />

Accuracy ±0.05% or better<br />

Zero drift ±0.3 µV/ °C<br />

Span drift ±25 ppm / °C<br />

Isolation-rated voltage 500 V DC<br />

CMR @ 50/60 Hz 150 dB<br />

NMR @ 50/60 Hz 100 dB<br />

Bandwidth 4 Hz<br />

Conversion rate 10 samples/sec.<br />

Input impedance 2 MΩ<br />

Digital output 2 channels open collector to 30 V<br />

sink current 30 mA max. load<br />

power dissipation 300 mW<br />

Digital input 1 channel<br />

logic level 0 +1 V max.<br />

logic level 1 +3.5 to +30 V<br />

pull up current<br />

Event counter<br />

0.5 mA<br />

Max. input frequency 50 Hz<br />

Min. pulse width 1 msec<br />

Watchdog timer Yes<br />

Power supply +10 to +30 V DC (non-regulated)<br />

Power consumption 1.2 W<br />

A-2 <strong>ADAM</strong> <strong>4000</strong> <strong>Series</strong> User's Manual