Table A-2 <strong>ADAM</strong>-4011 Range Accuracy for Thermocouple<br />

Input Range<br />

Code (Hex)<br />

0E J thermocouple 0 to<br />

760 C<br />

0F K thermocouple 0 to<br />

1000 C<br />

10 T thermocouple -100 to<br />

400 C<br />

11 E thermocouple 0 to<br />

1000 C<br />

12 R thermocouple 500 to<br />

1750 C<br />

13 S thermocouple 500 to<br />

1750 C<br />

14 B thermocouple 500 to<br />

1800 C<br />

Input Range Typical<br />

Accuracy<br />

Maximum<br />

Error<br />

Appendix A<br />

Units<br />

–0.5 –0.75 C<br />

–0.5 –0.75 C<br />

–0.5 –0.75 C<br />

–0.5 –0.75 C<br />

–0.6 –1.5 C<br />

–0.6 –1.5 C<br />

–1.2 –2.0 C<br />

Appendix A Technical Specifications A-3