4018M<br />

4.4.3 Analog Input Data Logger Command Set<br />

Command Syntax<br />

Command<br />

Name<br />

@AACCCSDMTTTT Set Memory<br />

Configuration<br />

@AAD Read Memory<br />

Configuration<br />

@AASO Set Memory<br />

Operation<br />

Mode<br />

@AAT Read Memory<br />

Operation<br />

Mode<br />

@AAL Event Record<br />

Count<br />

@AAN Standard<br />

Record Count<br />

@AARNNNN Read Record<br />

Content<br />

Chapter 4<br />

Description I/O Module<br />

Set the channel storage<br />

status, standalone mode, data<br />

logger mode, storage type and<br />

sampling interval for the<br />

specified analog input data<br />

logger.<br />

Return the configuration<br />

parameters for the specified<br />

analog input data logger.<br />

Start/stop the recording<br />

function of the memory<br />

module.<br />

Read the recording status of<br />

the memory module.<br />

Read the number of stored<br />

event records in the memory<br />

module.<br />

Read the number of stored<br />

standard records in the<br />

memory module.<br />

Read the contents of the<br />

specified record.<br />

@AAACSDHHHHTEIIII Set Alarm Limit Set the high/low alarm<br />

settings for the specified<br />

channel.<br />

@AABC Read Alarm<br />

Limit<br />

Read the high/low alarm<br />

settings for the specified<br />

channel.<br />