Table A-11 <strong>ADAM</strong>-4018/4018+ Range Accuracy for Thermocouple<br />

Input Range<br />

Code (Hex)<br />

0E J thermocouple 0 to<br />

760 C<br />

0F K thermocouple 0 to<br />

1000 C<br />

10 T thermocouple -100 to<br />

400 C<br />

11 E thermocouple 0 to<br />

1000 C<br />

12 R thermocouple 500 to<br />

1750 C<br />

13 S thermocouple 500 to<br />

1750 C<br />

14 B thermocouple 500 to<br />

1800 C<br />

Input Range Typical<br />

Accuracy<br />

Maximum<br />

Error<br />

Appendix A<br />

Units<br />

–1.0 –1.5 C<br />

–1.0 –1.5 C<br />

–1.0 –1.5 C<br />

–1.0 –1.5 C<br />

–1.2 –2.5 C<br />

–1.2 –2.5 C<br />

–2.0 –3.0 C<br />

NOTE: Because the CJC sensor of <strong>ADAM</strong>-4018/4018M is located in the<br />

side of channel 0 to 4, the measurement will have the difference ± 1 o C<br />

between channel 0 ~ 4 and channel 5 ~ 7.<br />