$AAAi<br />

Name CJC Setting<br />

Description This command configure the CJC setting.<br />

Syntax $AAAi(cr)<br />

$ is a delimiter character.<br />

AA (range 00-FF) represents the 2-character hexadecimal<br />

address. of the analog input module which is to be read.<br />

Ai represents the command code of CJC setting:<br />

If i=0, this command will stop CJC update.<br />

If i=1, this command will start CJC update.<br />

If i=2, this command will execute CJC update once only.<br />

(cr) is the terminating character, carriage return (0Dh).<br />

Response !AA(cr) if the command was valid.<br />

?AA(cr) if an invalid operation was entered.<br />

There is no response if the module detects a syntax error or<br />

communication error or if the specified address does not exist.<br />

! delimiter character indicates a valid command was received.<br />

? delimiter character indicates the command was invalid.<br />

AA (range 00-FF) represents the 2-character hexadecimal<br />

address of the analog input module.<br />

(cr) represents terminating character, carriage return (0Dh).<br />

Example command: $02A1(cr)<br />

response: !02(cr)<br />

The command starts the CJC update in the input module at<br />

address 02.<br />

4019<br />

Chapter 4 Command Set 4-75