Command Set 4021<br />

I2+<br />

I2-<br />

V2<br />

FGND<br />

V1<br />

I1-<br />

I1+<br />

NC<br />

INIT*<br />

(R) +Vs<br />

4-148 <strong>ADAM</strong> <strong>4000</strong> <strong>Series</strong> User's Manual<br />

(3) If Equal 4 mA Then Save Parameter<br />

( $020C2 ) And Goto Next Step Otherwise (1) Or (2)<br />

5. Reset Current Trim Data Variable To 0 ( $02G )<br />

6. Output 20 mA Current To Meter ( #02C2+20.000 )<br />

7. If Meter Is Not Equal 20 mA Then<br />

(1) If Higher Than 20 mA Then Trim Data Down<br />

( $023C281 )<br />

(2) If Lower Than 20 mA Then Trim Data Up<br />

( $023C201 )<br />

(3) If Equal 20 mA Then Save Parameter<br />

( $021C2 ) And Goto Next Step Otherwise (1) Or (2)<br />

8. Double Check 4 mA And 20 mA Is Right Or Not, If Wrong<br />

Then Re-Calibration, If Right Then Next Step<br />

9. Calibration OK !<br />

<strong>ADAM</strong>4024 Pin Define And Wiring Diagram:<br />

(Y) DATA+<br />

(G) DATA-<br />

(B) GND 10<br />

<strong>ADAM</strong>-4024 4CH AO Module<br />

I3+<br />

I3-<br />

V3<br />

FGND<br />

V4<br />

I4-<br />

I4+<br />

NC<br />

COM<br />

IDI4<br />

IDI3<br />

IDI2<br />

IDI1