4015, 4019<br />

$AA7CiRrr<br />

Name Single Channel Range Configuration<br />

Description This command configure the input type and range of the<br />

specified channel in an analog input module.<br />

Syntax $AA7CiRrr(cr)<br />

$ is a delimiter character.<br />

AA (range 00-FF) represents the 2-character hexadecimal<br />

address of the analog input module which is to be configured.<br />

7 represents the range configuration command.<br />

Ci represent the specified input channel you want to configure.<br />

Rrr represent the type and range you want to set. (refer to Table<br />

4-3 to check range code)<br />

(cr) is the terminating character, carriage return (0Dh).<br />

Response !AA(cr) if the command was valid.<br />

?AA(cr) if an invalid operation was entered.<br />

There is no response if the module detects a syntax error or<br />

communication error or if the specified address does not exist.<br />

! delimiter character indicates a valid command was received.<br />

? delimiter character indicates the command was invalid.<br />

AA (range 00-FF) represents the 2-character hexadecimal<br />

address of the analog input module.<br />

(cr) represents terminating character, carriage return (0Dh).<br />

Example command: $027C5R21(cr)<br />

response: !02(cr)<br />

The command configures the range of channel 5 in the analog<br />

input module at address 02 as Pt100 (IEC) 0~100oC.<br />

Chapter 4 Command Set 4-67