4015, 4019<br />

$AA8Ci<br />

Name Read Single Channel Range Configuration<br />

Description This command read the input type and range configuration of<br />

the specified channel in an analog input module.<br />

Syntax $AA8Ci(cr)<br />

$ is a delimiter character.<br />

AA (range 00-FF) represents the 2-character hexadecimal<br />

address of the analog input module which is to be read.<br />

8 represents the read range configuration command.<br />

Ci represent the specified input channel you want to read.<br />

(cr) is the terminating character, carriage return (0Dh).<br />

Response !AACiRrr(cr) if the command was valid.<br />

?AA(cr) if an invalid operation was entered.<br />

There is no response if the module detects a syntax error or<br />

communication error or if the specified address does not exist.<br />

! delimiter character indicates a valid command was received.<br />

? delimiter character indicates the command was invalid.<br />

AA (range 00-FF) represents the 2-character hexadecimal<br />

address of the analog input module.<br />

Ci represent the specified input channel you read.<br />

Rrr represent the type and range setting in the specified<br />

channel. (refer to Table 4-3 to check range code)<br />

(cr) represents terminating character, carriage return (0Dh).<br />

Example command: $028C5(cr)<br />

response: !02C5R21(cr)<br />

The command read the range of channel 5 in the analog input<br />

module at address 02. The response “R21” means Pt100 (IEC)<br />

0~100° C.<br />