4011, 4011D, 4012, 4013, 4015, 4016,<br />

4017, 4017+, 4018, 4018+, 4018M, 4019<br />

$AA2<br />

Example command: $452(cr)<br />

response: !45050600(cr)<br />

The command asks the analog input module at address 45h to<br />

send its configuration data.<br />

The analog input module at address 45h responds with an input<br />

range of 2.5 volts, a baud rate of 9600 bps, an integration time of<br />

50 ms (60 Hz), engineering units are the currently configured<br />

data format, and no checksum function or checksum generation.<br />

Chapter 4 Command Set 4-49